R to, Table 11, 6 electrical installation – Yaskawa AC Drive-Option BRAKING UNIT-CDBR Spec.D User Manual

Page 51

Advertising
background image

6 Electrical Installation

YASKAWA ELECTRIC TOBP C720600 01C 1000-Series Option CDBR-†D, LKEB-† Installation Manual

51

Wire Size and Torque Specifications

Select appropriate wire type and gauges from

Table 11

.

Note: 1. For main circuit terminal wiring ( , , B1, B2), UL approval requires using UL Listed copper wires

(rated at 75

°C (167°F)).

2. Use the wires with recommended gauge to make models 2022D, 2037D, 4030D, 4045D, and 5037D

conform to IP20 enclosure requirements.

Table 11 Wire Gauge and Torque Specifications

Model

CDBR- Terminal

For Japan

For U.S.A.

For Europe and

China

Screw

Size

Tightening

Torque

N

x

m

(lb.in.)

Recommended

Gauge

mm

2

Applicable

Gauge

mm

2

Recommended

Gauge

AWG, kcmil

Applicable

Gauge

AWG, kcmil

Recommended

Gauge

mm

2

Applicable

Gauge

mm

2

2022D
2037D
4030D
4045D
5037D

, ,

B1, B2

5.5

5.5 to 8.0

10

10 to 8

6

6 to 10

M5

2.7 to 3.0

(23.9 to 26.6)

IN1, IN2,

OUT1,
OUT2,

SB, SC,

MA, MB,

MC, EA,

EB, EC

0.75

0.75 to

2.00

18

18 to 14

0.75

0.75 to

2.50

M3.5

0.8 to 1.0

(7.1 to 8.9)

5.5

5.5 to 8.0

8

8

6

6 to 10

M5

2.0 to 2.5

(17.7 to 22.1)

2055D
4090D

, ,

B1, B2

14

14

8

8 to 6

10

10 to 16

M5

2.0 to 2.5

(17.7 to 22.1)

IN1, IN2,

OUT1,
OUT2,

SB, SC,

MA, MB,

MC, EA,

EB, EC

0.75

0.75 to

2.00

18

18 to 14

0.75

0.75 to

2.50

M3.5

0.8 to 1.0

(7.1 to 8.9)

14

14

6

6

10

10 to 16

M5

2.0 to 2.5

(17.7 to 22.1)

2110D
4220D
5110D
5300D

, ,

B1, B2

30

30 to 38

3

3 to 2

35

35

M8

8 to 10

(70.8 to 88.5)

IN1, IN2,

OUT1,
OUT2,

SB, SC,

MA, MB,

MC, EA,

EB, EC

0.75

0.75 to

2.00

18

18 to 14

0.75

0.75 to

2.50

M3.5

0.8 to 1.0

(7.1 to 8.9)

22

22 to 30

3

3 to 2

25

25 to 35

M8

8 to 10

(70.8 to 88.5)

TOBP_C720600_01C_3_0_E.fm 51 ページ 2013年10月7日 月曜日 午後2時20分

Advertising