7 Setting and Confirming CDBR Braking Unit Operation
YASKAWA ELECTRIC TOBP C720600 01C 1000-Series Option CDBR-D, LKEB- Installation Manual
55
Table 13 CDBR Enable/Disable Status (DIP Switch S1, S4)
Sink Mode (0 V Common), Internal Power Supply
Position DIP switch S1 for sinking as shown in
, when controlling the digital
SB-SC inputs by NPN transistors (0 V common/sinking mode) or contacts using the drive
internal power supply.
Figure 23
Figure 24 CDBR Braking Unit Sinking Mode using Internal Power Supply
DIP Switch S1-SINK/
SOURCE
DIP Switch S4-SB/SC
Terminals N.O./N.C.
SB-SC-Enable Input
CDBR Status
SINK
A
Open
Enabled
SINK
A
Close
Disabled
SINK
B
Open
Disabled
SINK
B
Close
Enabled
SOURCE
A
0 V Input
Enabled
SOURCE
A
24 V Input
Disabled
SOURCE
B
0 V Input
Disabled
SOURCE
B
24 V Input
Enabled
+24 V
SINK-default
SOURCE
SB
SC
S4
S1
A (N.O. (default))
B (N.C.)