Diagnostics & Troubleshooting 6 - 3

Table 6.1 Fault Displays and Processing (continued)

Digital

Operator Display

Description

Cause

Corrective Action

CPF05

External A/D Err

External A/D Converter Fault

Noise or spike was on the
control circuit input terminals.

Perform a factory initialization.

Cycle power to the Drive.

Replace the control board.

CPF06

Option Error

Option Board Connection Error

The option board was not
connected properly.

Turn off the power and reinstall
the option board.

The Drive or option board was
damaged.

Replace the option board or the
Drive.

CPF07

RAM-Err

ASIC Internal RAM Fault

Control circuit failure/damage.

Cycle power to the Drive.

Control circuit damage.

Replace the Drive.

CPF08

WAT-Err

Watchdog Timer Fault

Control circuit failure/damage.

Cycle power to the Drive.

Control circuit damage.

Replace the Drive.

CPF09

CPU-Err

CPU-ASIC Mutual Diagnosis Fault

Control circuit failure/damage.

Cycle power to the Drive.

Control circuit damage.

Replace the Drive.

CPF10

ASIC-Err

ASIC Version Fault

Control circuit damage.

Replace the Drive.

CPF20

Option A/D Error

Option Card Fault

Option board input fault.

Remove all inputs to the option
board.

Option card A/D convert fault.

Perform a factory initialization.

Cycle power to the Drive.

Replace the option board.

Replace the control board.

CPF21

Option CPU Down

Self-diagnosis Fault of Option Board

Noise or spike was on the
communication line and/or
defective option board.

Perform a factory initialization.

Cycle power to the Drive.

Replace the option board.

Replace the control board.

CPF22

Option Type Err

Option Board Code Number Fault

Unrecognizable option board
was connected to the control
board.

Remove any option boards.

Cycle power to the Drive.

Perform a factory initialization.

Replace the option board.

Replace the control board.

CPF23

Option DPRAM Err

Option Board Interconnection Fault

An option board was not
correctly connected to the
control board, or an option
board that was not made for
the Drive was attached to the
control board.

Remove power to the Drive.

Reconnect the option board.

Perform a factory initialization.

Cycle power to the Drive.

Replace the option board.

Replace the control board.