Initial Installation

QUALIFIED INSTALLERS ONLY

Figure 12. Possible Vent Configurations for Top Vented; Vertical and

Horizontal Terminations.

NOTE: The total length of the vent pipes can not exceed 30

feet (9.14 m). Any combination of rise and run can be

used as long as it lays within the shaded area (a total

of three (3) 90° elbows or six (6) 45° elbows can

be used). In addition to what is shown, if a 90°

elbow is used in the horizontal plane, 3 feet

(91.4 cm) must be subtracted from the

allowable horizontal run (for each 45°

elbow, 11⁄2 feet must be subtracted

from the allowable horizontal

run).

Slide the hex head bolt to the next

setting and re-tighten the bolt to

secure in place.
The numbers in this chart represent

the actual vent restrictor settings.

Although the numbers do not

appear on the unit use this as a

guide to follow.
Undo the setscrew and adjust the

restrictor to the correct setting.
Ensure that the setscrew is re

tightened and the unit is checked

for proper operation.
Wait for unit to warm up to operating

temperature to ensure proper and

clean burning unit.
Note: 0,0 in Figure 12 represents

a 90˚ bend directly off the outlet of

the unit, in all horizontal instances

except when using Selkirk and

having less than a 4 ft (1.22 m)

rise and 8 ft (2.44 m) horizontal

offset. In this case, a 1 foot (30.5

cm) rise must be added below the

90˚ bend.

15

P

LANNING

Y

OUR

I

NSTALLATION

:

When planning your installation, it will be necessary to select the proper length of vent pipe for your

particular requirements. It is important to note when passing through a wall, the maximum allowable

wall thickness is 10 inches (25.4 cm), 11⁄2 inches (3.8 cm) clearance to combustibles must be maintained.

Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine

the length of vent pipe required for vertical installations, measure the distance from the appliance flue

outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow

for sufficient vent height above the roof line. For two story applications, a fire stop is required at each

floor level. If an offset is needed in the attic, additional pipe and elbows will be required. To connect the

venting system to the appliance flue outlet, a twist-lock adapter is built into the appliance at the factory.

Refer to ‘Vent Configuration and Restrictor Settings’ for venting parameters.