40 huawei – Solare Datensysteme Solar-Log User Manual

Page 124

Advertising
background image

124

Huawei

Huawei

40 Huawei

40�1 Huawei

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

•

Integrated interface

•

Where to connect: RJ45 socket on the outside of the inverter

•

2-pin wiring

•

Communication address must be allocated.

•

Installation steps

•

Switch off the inverters and Solar-Log™

•

Connect inverters to the Solar-Log™

•

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

•

self-made cable connection with RS485 data cable and terminal block connector.

Procedure

•

Open the inverter as shown in the inverter's instructions.

•

Insert the RJ45 plug into RS485-Out socket on the inverter.

•

If you are making the cable yourself, connect the wires as shown in the following diagram

•

Address the inverter according to the manufacturer's specifications.
Address range 1 to 247.

•

If only one inverter is to be connected, it must be terminated according to the manufacturer‘s instruc-

tions.

•

Close the inverter if no other inverters are to be connected.

•

Insert the terminal block connector into the Solar-Log™ RS485 socket.

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

1 or 4

► 4

2 or 5

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

►

Only connect inverters via the RS485/422 Solar-Log™ interface(s).