Note

Conergy inverters can only be connected to the Solar-Log 1000 and 2000, as only this one
has a CAN interface.

The following description relates to inverters without transformers produced in or after 2007.

Easy Installation

Termination

Addressing

Interface

No

Yes

No

CAN bus

Overview

•

CAN only to be used on Solar-Log 1000 and 2000 (CAN interface).

•

Integrated interface

•

Where to connect: CAN socket on the outside of the bottom of the inverter.

•

Only use ready-made cable sets.
Two different special cable sets must be ordered separately.

-

Prefabricated cable set between the Solar-Log 1000 and 2000 and the first inverter, including

cable termination.

-

Ready-made cable set with 5 pin Phoenix contact connection plug for connecting the inverters to

each other.

-

Depending on the number of inverters several of these cables will be required.

Maximum total cable length: 200 m

•

Communication address does not have to be assigned

•

Installation steps

•

Switch off the inverters and Solar-Log™

•

Connect inverters to the Solar-Log™

•

Connect the inverters to each other

Connect the inverters to the Solar-Log 1000 and 2000�

Connection is only done using a ready-made data cable, specially for connecting to the Solar-Log 1000

and 2000 (optional extra; not supplied).

Procedure

1.

Insert the CAN plug into the inverter CAN IN socket.

2. If only one inverter is to be connected this must be terminated.

Insert the two 5 pin 120

Ω terminal resistors from the ready-made cable set into the CAN OUT socket.

3. Insert the terminal block connector into the Solar-Log 1000 and 2000 CAN socket.