Solare Datensysteme Solar-Log User Manual

Page 258

Advertising
background image

258

Steca

Steca (larger than 17k)

83�2 Steca (larger than 17k)

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

•

Integrated interface

•

Where to connect: RJ45 socket on the bottom of the inverter

•

2-pin wiring

•

Communication address must be allocated.

•

Installation steps

•

Switch off the inverters and Solar-Log™

•

Connect inverters to the Solar-Log™

•

Connect the inverters to each other

Select the Steca >=17k inverter during the initial configuration.

Note

To use active and reactive power management, all of the inverters need to be set to:

•

Protocol 1

•

57600 baud

•

Parameter 1164 = 2

Connect inverters to the Solar-Log™

The wiring is done using a

•

self-made, shielded 2 wire data cable and terminal block connector.

Procedure

•

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

RS485 inverter socket

Terminal

PIN

► 1

► 2

► 4

► 3

•

If only one inverter is to be connected this must be terminated.
On the sockets "RS485 OUT" with SACC-M12MS-4SC round plugs bypass the connections PIN1 to
PIN2 and PIN3 to PIN4.

•

Close the inverter if no other inverters are to be connected.

•

Insert the terminal block connector into the Solar-Log™ RS485 socket.