SolaX Power

SolaX Power X1

Procedure

1.

If you make the cable yourself, connect the wires as shown in the following diagram.

Solar-Log™ terminal strip connector

RS485 inverter socket

Terminal

PIN

► 1

► Pin 3 - TX+

► 4

► Pin 6 - TX-

► 5

► Pin 1 - RX+

► 6

► Pin 2 - RX-

2. Insert the RJ45 plug into any RJ45 socket on inverter 1.

3. If only one inverter is to be connected, terminate it according to the inverter instructions.

4. Insert the terminal block connector into the Solar-Log™ RS485/422 B or RS485/422 C socket.

Connect the inverters to each other

Connect using a RJ45 cable (patch cable).

Where to connect: RJ45 socket.

Procedure

1.

Insert the self-made cable with the RJ45 plug into any RJ45 socket on inverter 1. Connect the other

end to the terminal plug on the Solar-Log™.

2. Insert the RJ45 cable into the 2nd RJ45 socket on inverter 1 and into any RJ45 socket on

inverter 2.

3. Connect the other inverters to each other in the same way.

4. Insert the terminal block connector into the Solar-Log™ RS485/422 B/C socket.

5. Terminate in the last inverter in accordance with the inverter instructions.