19 delta – Solare Datensysteme Solar-Log User Manual

Page 72

Advertising
background image

72

Delta

Delta (RS485)

19 Delta

19�1 Delta (RS485)

Easy Installation

Termination

Addressing

Interface

Yes

Resistor

Yes

RS485

Overview

•

Integrated interface

•

Where to connect: RJ45 socket on the outside of the inverter

•

2-pin wiring

•

Communication address must be allocated.

•

Installation steps

•

Switch off the inverters and Solar-Log™

•

Connect inverters to the Solar-Log™

•

Connect the inverters to each other

•

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

•

ready-made Delta data cable (optional extra; not supplied)

or

•

self-made cable connection with RS485 data cable and terminal block connector.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

►

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► 7

► 4

► 6

► 4

► 8

Note

The PIN allocation has been changed with the new generation. 3 wired cabling functions
with both generations.

Advertising