259

Steca

Steca (larger than 17k)

Connect the inverters to each other

Connect using

•

a 2-wire shielded data cable and

•

4-pin Phoenix Contact Connection plug type "M12MS SACC-4SC SH“ (two plugs included with the
inverter).

•

Where to connect: RS485 sockets on the bottom of the inverter.

The RS485 IN and OUT sockets are each double connections so that the wiring can be continued to the

next inverter.

Procedure

•

Wiring the data cable to the "Phoenix Contact Type M12MS SACC-4SC SH“ according to the manu-
facturer's instructions.

•

Insert one plug into the OUT (X14B) socket of inverter 1.

•

Insert the other end of the wire into the IN socket (X15B) on inverter 2.

•

Connect the other inverters to each other in the same way.

•

Terminate in the last inverter.
On the sockets "RS485 OUT" with Phoenix contact type M12MS SACC-4SC SH bridge the connec-
tions PIN1 to PIN2 and PIN3 to PIN4.

•

Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

highest possible address: 31

Set the following parameters on the inverter's operating display:

•

Press "F1", select

Numerical list

, press "ENTER".

•

Set parameter number

2000

[password protection],

press "ENTER" twice.

•

Enter

72555

, press "ENTER"

•

Set parameter number

0406

, press "ENTER"

•

Select sub parameter

0406,3

, press "ENTER"

•

Enter figure for communication

x

[

x

= continuous numbering starting with 1; highest possible address: 31], press "ENTER". 31], press

"ENTER".

After configuring on the display:

•

Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are
activated.

•

Set the date and time on the inverter as shown in the inverter instructions.