Voltage Measurement (Auto ranging)

Range

Accuracy

Resolution

Input Impedance

15 – 310V

±(0.5%+2digit)

0.2V

300kΩ(phase-neutral)

600kΩ (phase-phase)

310 – 600V

0.4V

Voltage Anomalies Detection (Manual Selection of Range)
Voltage

Range

Accuracy

Resolution

Input Impedance

15 – 310V

±(0.5%+2digit)

0.2V

300kΩ (phase-neutral)

600kΩ (phase-phase)

310 – 600

0.4V

Time

Accuracy (ref. to 60Hz)

Resolution

±8.33ms (½ period of fundamental)

8.33ms (½ period of fundamental)

Current measurement (DM-II Plus only)

Range

Accuracy

Resolution

Input Impedance

Protection against

overloads

0.005-0.26V

±(0.5%+2digit)

0.0001V

100kΩ

5V

0.26-1V

0.0004V

Current measurement (Using DM-Ct-HtA)

Range

Accuracy

Resolution

Protection against overloads

5 to 1000 A

±(1.5% of range)

0.1 A

600 V

Minimal Current measurable is equal to 1.5% of Clamp Full Scale

Current measurement (Using ACf-3000 SR)

Range

Accuracy

Resolution

Protection against overloads

15 to 3000 A

±(1.5% of range)

0.1 A

600 V

Minimal Current measurable is equal to 1.5% of Clamp Full Scale