Power measurement (cosϕ: 0.5c[positive] – 0.5i[negative])

Value

Ranges

Accuracy

Resolution

Active power

0 – 999.9W

1kW – 999.9kW

1MW – 999.9MW

±(1.5%+2digit)

0.1W

0.1kW

0.1MW

Reactive power

0 – 999.9VAR

1kVAR – 999.9kVAR

1MVAR – 999.9MVAR

0.1VAR

0.1kVAR

0.1MVAR

Apparent power

0 – 999.9VA

1kVA – 999.9kVA

1MVA – 999.9MVA

0.1VA

0.1kVA

0.1MVA

Active energy

0 – 999.9Wh

1kWh – 999.9kWh

1MWh – 999.9MWh

0.1Wh

0.1kWh

0.1MWh

Reactive energy

0 – 999.9VARh

1kVARh – 999.9kVARh

1MVARh – 999.9MVARh

0.1VARh

0.1kVARh

0.1MVARh

Cosϕ Measurement

Cosϕ

Resolution

Accuracy (expressed in degrees)

0 to 0.20

0.01

0.6

0.21 to 0.50

0.7

0.51 to 0.80

1

Measurement of Harmonics
Voltage

Range

Accuracy

Resolution

DC – 25h

26h – 33h
34h – 49h

±(5.0%+2digit)

±(10.0%+2digit)
±(15.0%+2digit)

0.1V

The voltage harmonics will be null under the following threshold:
- DC: if <1V or <2% of 1st harmonic
- 1st harmonic: if <2V
- 2nd to 49th: if <1V or <2% 1st harmonic

Current

Range

Accuracy

Resolution

DC – 25h

26h – 33h
34h – 49h

±(5.0%+2digit)

±(10.0%+2digit)
±(15.0%+2digit)

0.1A

The current harmonics will be null under the following threshold:
- DC: if <2% of 1st harmonic or < 0.2% of clamp full scale
- 1st harmonic: if < 0.2% of clamp full scale
- 2nd to 49th: if <2% 1st harmonic or < 0.2% of clamp full scale
Setting the FLEX option the DC component will be ignored.