Amprobe DM-II-PLUS Power-Quality-Recorder User Manual

Page 26

Advertising
background image

24

Message

Description

Advices

No parameter se-
lected

A recording has been started without
selecting values to be recorded

Push START/STOP, and se-
lect at least one value from
the MENU

No Phase selected

Voltage and/or current harmonics have
been selected and the corresponding
flag has been enabled (HARMONICS
ON) but no phase voltage or current has
been selected

Select at least one phase
voltage and/or current

PASSWORD ERROR

The password entered is wrong

Insert the password: F1, F4,
F3, F2

PASSWORD OK

The password is correct

Please wait

The instrument is waiting for the record-
ing to start

Recording

The instrument is recording

Too many param

More than 63 parameters have been
selected (harmonics included) or more
than 38 parameters with COGENERA-
TION Flag enabled

Deselect parameters

Too many record

The quantity of recorded data + Smp
exceeds the maximum allowed (35)

Transfer recordings to a PC
and then clear the instru-
ment memory

ERR: SEQ

The Phase Sequence is wrong.

Check the Phase Sequence
connection.

ERR: P-

The active powers on the right side of
the message are negative

Check if the clamps are
properly connected, unless
co-generation is involved

ERR: SEQ & P-

The active powers on the right side of
the message are negative and the Phase
Sequence is wrong.

Check if the clamps are
properly connected / check
the Phase Sequence con-
nection, unless co-genera-
tion is involved

ERR: CONNECTION

The Voltage inputs are not connected
correctly.

Check the Voltage connec-
tions (see Physical Connec-
tions, Page X8)

Error Vref

A Voltage reference was selected that is
not compatible with voltage input.

Check Voltage Reference
set in RECORDER CONFIG
in MENU

Error1 to Error 5

The instrument memory is damaged.

Contact Amprobe for as-
sistance