TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

11

62-0278—07

Fig. 24. Installer Setup (IS) mode screen.

M27585

Setup

Table 4. Installer Setup (IS) Codes and Options.

IS

Code Code Description

Option

Value

Option Description (Default value shown in

Bold)

Notes

1

Line Voltage

Selection

0

120 Vac power supply (Default)

1

240 Vac power supply

2

System Type

0

Heat only

1

Cool only

2

Two pipes: Heat or Cool; Manual Changeover

3

Two pipes: Heat or Cool; Seasonal Changeover

(requires optional pipe sensor)

4

Four pipes: Manual Changeover

TB6575A, TB6575C and

TB8575A only

5

Four pipes: Auto Changeover

TB6575A, TB6575C and

TB8575A only

6

Two pipes: Heat or Cool; with Auxiliary Heat

(requires optional pipe sensor).

Allows auxiliary heat to turn

on when pipes have cold

water

(TB6575A, TB6575C and

TB8575A only).

7

Four pipes: Manual and Auto Changeover

(Default)

TB6575A, TB6575C and

TB8575A only

2.5

Fan On/Off

Selection for Aux

Heat On

0

Fan ON when Auxiliary Heat is on (Default)

Enables or disables the

auto fan operation when

Auxiliary Heat is On

(TB6575A, TB6575C and

TB8575A only).

1

Fan OFF when Auxiliary Heat is on

3

Valve Output Type

0

N.C. (normally closed) - ON/OFF (Default)

1

N.O. (normally open) - ON/OFF

4

Sensor Type

0

Onboard Sensor (Default)

1

Remote Sensor (TR21 or other 20K Ohm sensor)

5

Pipe Sensor

0

Default mode is Heat:

N.O. (normally open) Input.

Only displays when system type 3 or 6 is selected.

The Pipe Sensor code

automatically displays

based on the System Type

(IS code #2) selection. For

example, only when you

select the value 3 or 6 for

the System Type, will the

Pipe Sensor code and its

values display.

Pipe sensor will flash on

display screen if analog

input (#4) is lost.

Pipe sensor status and

water temperature can be

checked in test mode (see

“Installer Test (IT) Mode” on

page 13 for details)

1

Default mode is Cool:

N.O. (normally open) Input.

Only displays when system type 3 or 6 is selected.

2

Default mode is Heat:

N.C. (normally closed) Input.

Only displays when system type 3 or 6 is selected.

3

Default mode is Cool:

N.C. (normally closed) Input.

Only displays when system type 3 or 6 is selected.

4

Analog input (Default). NTC20K, whose curve is

the same as TR21.

Only displays when system type 3 or 6 is selected.