TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

3

62-0278—07

Fig. 1. Dimensions in inches (mm).

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-

ous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for

your application.

3. Installer must be a trained and experienced service

technician.

WARNING

Risk of electrical shock.

Can cause severe injury, property damage or

death.

Disconnect power supply before installation and

before servicing.

IMPORTANT

The thermostats are line voltage powered devices. All

wiring must comply with national and local electrical

codes, ordinances and regulations. Provide disconnect

means and overload protection, as required.

The TB8575A1000 thermostat must be powered by an

Approved 24 Vac, Class 2, NEMA rated transformer

(such as a W6380 Relay Control Center).

Location

The thermostats are the temperature control element in a

fan coil or air-conditioning system. They must be located

about 1.5m (5 ft.) above the floor, in a position with good

air circulation, to sense room temperature.

IMPORTANT

Do not mount the device where it can be affected by:

1. Drafts or dead spots behind doors or in corners.

2. Hot or cold air from ducts.

3. Radiant heat from the sun or appliances.

4. Unheated (uncooled) areas such as an outside

wall behind the thermostat.

5. Concealed pipes or chimneys.

Mounting and Wiring

CAUTION

Equipment damage hazard.

Operation at low temperatures can cause fan

coil damage.

This thermostat is not a safety device. Do not use

it where the space temperature is outside of the

device operating range.

A display of two dashes, – –, for the Room Temp

display indicates a sensor failure or a temperature

outside of the thermostat operating range of 18°C

to 49°C (0°F to 120°F). With – – displayed, the

thermostat ceases to operate. When the

temperature returns to within its operating limits,

the thermostat returns to operation.

The optional freeze protect feature should be used

if low temperatures can occur.

The thermostat must be mounted flush to the wall. The

thermostat can be mounted directly to a 2 x 4 in.

horizontal junction box (see Fig. 2 on page 4). An optional

adaptor plate (50033847-001) can be used with a 4 x 4 in.

or a vertical junction box for which mounting screws are

supplied (see Fig. 3 on page 4).

1. Prepare the supply wires:

a. Mounting on a 4 x 4 in. or vertical 2 x 4 in.

junction box:

(1) Feed the supply wires through the junction

box and the opening in the adaptor plate.

(2) Affix the adaptor plate to the junction box

using the screws provided.

b. Mounting on a horizontal 2 x 4 in. junction box:

Feed the supply wires through the opening of the

junction box.

2. Attach the supply wires:

a. For the TB6575A1000, TB6575B1000 and

TB6575C1000 models:

(1) Push the fly lead wires through the wiring

access hole in the sub-base.

(2) Attach the fly lead wires to the supply wires

using wire nuts (not provided).See Table 3

on page 5 for terminal and lead identifica-

tion.

(3) Push the fly lead and supply wires back into

the junction box.

b. For the TB8575A1000 model (which does not

have pre-wired fly leads):

a

The five relays are wired via terminals W, Y, Gh, Gm, and Gl. Relay 1 controls Heat open (W) or Cool open (Y). Relay

2 controls Cool open or Electrical heater output (Y/A). Relays 3, 4, and 5 control the High, Medium, and Low fan

speeds respectively (Gh, Gm, and Gl).

NOTE: In 2-pipe configurations without Auxiliary Heat, only 4 relays are used; relay 2 (Y/A) is not used.

b

Pipe sensor is required for 2 pipe auto changeover and 2 pipe auxiliary heat applications.

M27589

UP

5-13/16 (148)

3-13/16

(97)

1-1/8

(29)

THERMOSTAT

SUB-BASE

3-1/4 (83)

2-3/8 (60)

1-3/4

(44)

5/32

(4)

5/32

(4)

1-3/16

(30)