TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

18

Both the heating and

cooling equipment are

running at the same

time.

Incorrect System Type

selected.

Check that the Installer Setup code #2 (System Type) value

matches the installed heating and/or cooling equipment.

Heating and cooling wires

are shorted together.

Separate the shorted heating and cooling wires.

Cooling does not turn

on (Cool On is solid in

the display).

Cooling equipment failure. For TB6575A/B/C:

1. Check for 120/240/277 Vac at the equipment between power

and common, (terminals L and N).

2. Check for 120/240/277 Vac between the cool (Y) and com-

mon (N) terminals. If 120/240/277 Vac is present, the ther-

mostat is functional.

For TB8575A:

1. Check for 24 Vac at the equipment on the secondary side of

the transformer between power and common (terminals R

and C).

2. Check for 24 Vac between the cool terminal (Y) and trans-

former common. If 24 Vac is present, the thermostat is func-

tional.

If voltage is present, check the cooling equipment to find the cause

of the problem.

Loose connection or

broken wire between

thermostat and cooling

equipment.

For TB6575A/B/C:

Check for 120/240/277 Vac between the cool (Y) and common

(N) terminals.

For TB8575A:

Check for 24 Vac between the cool terminal (Y) and transformer

common.

If voltage is not present, check the wire connection (loose or

broken) between the thermostat and the cooling equipment.

Fan does not turn on

in a call for Heat.

Wiring or connection

failure

Check wiring and make sure the connection is correct.

Cannot select fan

speed.

Fan Control Type

selection is incorrect.

Check that the Installer Setup code #9 (Fan Control) value is set to

zero (0).

Heating equipment is

running in the Cool

mode.

Incorrect System Type

configured.

Check that the Installer Setup code #2 (System Type) value

matches the installed heating and/or cooling equipment.

Heating equipment

does not turn off and

heat temperature

setting is set below

room temperature

(Heat On is not in the

display).

Incorrect System Type

configured.

Check that the Installer Setup code #2 (System Type) value

matches the installed heating and/or cooling equipment.

Cannot set the system

setting to Heat.

System Type (Installer

Setup code #2) is set to

Cool Only (value = 1).

Set the Installer Setup code #2 value to match the installed heating

and/or cooling equipment.

Cannot set the system

setting to Cool.

System Type (Installer

Setup code #2) is set to

Heat Only (value = 0).

Set the Installer Setup code #2 value to match the installed heating

and/or cooling equipment.

Heat On is not in the

display.

System Type setting is not

set to Heat and/or the

temperature setting is not

set above the room

temperature.

Set the Installer Setup code #2 to Heat and set the temperature

setting above the room temperature.

Cool On is not in the

display.

System Type setting is not

set to Cool and/or the

temperature setting is not

set below the room

temperature.

Set the Installer Setup code #2 to Cool and set the temperature

setting below the room temperature.

Remote sensor does

not display

temperatures

Incorrect IS code.

Set the Installer Setup code #4 to Remote (value = 1).

Sensor is not compatible. The remote sensor must be TR21 or compatible 20K NTC.

Table 8. Troubleshooting. (Continued)

Symptom Possible

Cause

Action