TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

6

Accessory Wiring

Remote Pipe Sensor Wiring

The remote pipe sensor is used for 2 pipes auto and 2

pipes heat and cool with auxiliary heat changeover. The

pipe sensor will sense the temperature in the pipes to tell

the thermostat when the system is set for Heat or Cool.

1. Check Installer Setup Number (ISU) 5 to ensure it is

set to the desired value. (See Table 4 on page 11).

2. Wire pipe sensor to Sc and Ps terminals.

3. Attach pipe sensor to the pipe.

4. Insulate pipe sensor, as necessary.

5. Change pipe sensor thresholds for cooling or heat-

ing by setting Installer Setup Numbers (ISU) 6 and

7 to desired values.

Remote Temperature Sensor Wiring

The TR21 is an optional remote temperature sensor that

can be used as an alternative to the internal sensor. In

addition to the TR21, other Honeywell sensors that use a

20k Ohm curve may be used as the remote sensor.

WARNING

Risk of electrical shock.

Can cause severe injury, property damage or

death.

Disconnect power supply before servicing.

CAUTION

Erratic system operation hazard.

Failure to follow proper wiring practices can

introduce disruptive electrical interference

(noise).

Keep wiring at least one foot away from large

inductive loads such as motors line starters,

lighting ballasts, and large power distribution

panels. Shielded cable is required in installations

where these guidelines cannot be met. Ground

shield only to grounded controller case.

IMPORTANT

All wiring must comply with local electrical codes and

ordinances or as specified on installation wiring dia-

grams.

— Wall module wiring can be sized from 16 to 22

AWG (1.31 to 0.33 sq. mm) depending on the

application.

— The maximum length of wire from the thermostat

to a wall module is 1000 ft. (305 m).

— Twisted pair wire is recommended for wire runs

longer than 100 ft. (30.5 m).

1. Check Installer Setup Number (ISU) 4 to ensure it is

set to use the remote sensor. (See Table 4 on

page 11).

2. Wire sensor to Rs and Sc thermostat terminals.

3. Push excess wire back into the hole. Plug the hole

using non-hardening caulk, putty or insulation to

prevent drafts from affecting performance.

4. Remove sensor cover.

5. Mount sensor to the wall or junction box using the

screws and anchors provided.

6. Level the sensor for appearance only. Device func-

tions correctly even when not level.

7. Replace sensor cover.

NOTE: For complete wiring instructions, please

follow the installation instructions provided

with the remote sensor.

Sensor Wiring for Temperature

Averaging

Fig. 4–Fig. 6 illustrate sensor wiring for temperature

averaging applications.

Fig. 4. Wiring four TR21 (20K ohm) sensors.

Fig. 5. Wiring two TR21-A (10K ohm) sensors to

provide a temperature averaging network.

Fig. 6. Wiring two TR21 (20K ohm) sensors and

one TR21-A (10K ohm) sensor to provide

a temperature averaging network.

M27559

Rs

Sc

T T

SUBBASE

TR21

T T

TR21

T T

TR21

T T

TR21

M27560

Rs

Sc

SUBBASE

TR21-A

T4 T3

TR21-A

T4 T3

1

1

1

THE TR21-A IS A 10K OHM SENSOR.

M27561

T4

T3

TR21-A

1

1

THE TR21-A IS A 10K OHM SENSOR.

Rs

Sc

T

T

SUBBASE

TR21

T

T

TR21