TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

12

6

Pipe Sensor

Threshold for

Cooling

50 to

72

Range is 50°F to 72°F.

Default is 60°F.

Changes to Cool when pipe

temperature is below

threshold.

7

Pipe Sensor

Threshold for

Heating

75 to

90

Range is 75°F to 90°F.

Default is 80°F.

Changes to Heat when pipe

sensor temperature is

above threshold.

8

Temperature Scale

0

Degrees Fahrenheit (°F); Default.

1

Degrees Celsius

(°C).

8.5 Fan Speed at motor

start up

0

Provide full power when fan motor starts –

always starts in high fan speed (Default)

High speed start up

ensures that there is

enough torque to start the

motor and eliminates and

motor locking.

1

Disable – fan will start at speed that is needed as

defined by VersaSpeed

9

Number of Fan

Speeds

1

Single Speed Fan

Low speed only

2

2 Speed Fan

Hi and Low speed fans only

3

3 Speed Fan (Default)

Hi, Med, and Low speed fan

9.5 Fan Control Type

0

Constant and Auto (Default)

When fan is in Auto, the fan

ramping algorithm,

Veraspeed, is used

1

Auto only

10

Control Method for

4-Pipe Auto

Changeover

1

Single Setpoint (Default)

Uses switching differential

to change between heating

and cooling and controls to

a single setpoint (Only

displayed for system types

5 or 7)

2

Heat and Cool Setpoints (2 setpoint method)

Uses a deadband of no

control and controls to a

heat or cool setpoint. (Only

displayed for system types

5 or 7)

10.5 Deadband for Heat/

Cool Setpoints

2 to 9 Range is 2 to 9.

Default is 3. Deadband = minimum

distance between heating and cooling setpoints.

Available when Heat and

Cool Setpoints are chosen

for the control method for 4-

pipe Auto (ISU 10)

Switching

Differential for

Single Setpoint

2 to 6 Range is 2 to 6.

Default is 3. Heat switching point =

setpoint - switching differential. Cool switching point

= setpoint + switching differential.

Available when Single

Setpoint is chosen for the

control method for 4-pipe

Auto (ISU 10)

11

CPH Value for Heat 1 to 12 Range is 1 to 12.

Default is 4.

The number selected

indicates the maximum

times Heating is cycled on

per hour (CPH).

12

CPH Value for Cool 1 to 6 Range is 1 to 6.

Default is 3.

The number selected

indicates the maximum

times Cooling is cycled on

per hour (CPH).

13

CPH for Auxiliary

Electrical Heater

1 to 12 Range is 1 to 12.

Default is 6.

The number selected

indicates the maximum

times Auxiliary Heating is

cycled on per hour (CPH).

14

Display

Temperature

Adjustment

-4 to 4 Range is -4°F to +4°F;

Default is 0°F.

15

Temperature

Display Mode

0

Display Room Temperature

1

Display Setpoint

2

Display Temperature and Setpoint; Default.

16

Setpoint Range

Stop for Heating

50 to

90

Range is 50°F to 90°F.

Default is 90°F.

Table 4. Installer Setup (IS) Codes and Options. (Continued)

IS

Code Code Description

Option

Value

Option Description (Default value shown in

Bold)

Notes