TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

9

62-0278—07

Fig. 17. Two pipes (Heat or Cool) auto changeover

wiring diagram (24 Vac shown).

Fig. 18. Four pipes (Heat and Cool) Manual/Auto

Changeover wiring diagram (24 Vac shown).

Fig. 19. Two pipes (Heat or Cool) with Auxiliary Heat

and Manual Changeover wiring diagram (24 Vac

shown).

.

Fig. 20. Wiring diagram when missing a wire for

electromechanical retrofit (24 Vac shown).

Removing the Thermostat

WARNING

Risk of electrical shock.

Can cause severe injury, property damage or

death.

Disconnect power supply before servicing.

CAUTION

Equipment damage hazard.

Improper removal can damage the thermostat.

Carefully follow the thermostat removal directions.

If it is necessary to remove the thermostat from the sub-

base, refer to Fig. 21 and perform the following steps:

1. Turn off the thermostat by pressing the system

button until OFF displays.

2. Remove the power source from the thermostat.

3. Remove the small safety screw at the bottom of the

thermostat.

4. Use both hands to pull the thermostat straight away

from the sub-base.

24 VAC

M27576

VALVE

FAN

L1

(HOT)

L2 1

REMOTE SENSOR

REMOTE SETBACK

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

PIPE SENSOR

R

W/Y

Y/A

GI

Gm

Gh

C

Rs

Sc

SB

Ps

24 VAC

M27577

HEAT VALVE

FAN

L1

(HOT)

L2 1

REMOTE SENSOR

REMOTE SETBACK

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

COOL VALVE

R

W/Y

Y/A

GI

Gm

Gh

C

Rs

Sc

SB

Ps

24 VAC

M27578

VALVE

FAN

L1

(HOT)

L2 1

REMOTE SENSOR

REMOTE SETBACK

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

PIPE SENSOR

AUX

R

W/Y

Y/A

GI

Gm

Gh

C

Rs

Sc

SB

Ps

24 VAC

M31329

HEAT VALVE

FAN

COOL VALVE

REMOTE SETBACK

REMOTE SENSOR

L1

(HOT)
L2

5

3

4

1

2

1

2

REMOVE PRE-WIRED WIRE FROM TERMINAL 5 (MID FAN SPEED).
JUMPER TERMINALS 5 AND 6 (MID AND HIGH FAN SPEEDS). FAN

MEDIUM SETTING WILL OPERATE ON HIGH SPEED.
CONNECT TERMINAL 7 TO THE MID FAN SPEED WIRE FROM

PREVIOUS SYSTEM.
REWIRE THE PREVIOUS MID FAN SPEED WIRE TO THE NEUTRAL

CIRCUIT IN THE SYSTEM.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

CHANGE INSTALLER SETUP IS CODE 9 TO 2 FOR

2 SPEED FAN CONTROL.

3

4

5

6

6

L

W/Y

Y/A

GI

Gm

Gh

C

Rs

Sc

SB

Ps