TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

16

2 Pipes with Auto Changeover

For this application the system switch only provides "Off"

and "Auto". When in "Auto" mode the water temperature

will indicate if the thermostat should operate in heating or

cooling.

Operation:

After exiting the installer setup, the thermostat will perform

a 5 minute purge. During this initial 5 minute purge, the

valve (W/Y) will energize and the fan will be de-energized.

After the 5 minute purge, the thermostat will go into the

appropriate mode as described in Table 6.

Table 6. Logic for 2 Pipes with Auto Changeover

*If pipe temperature is between the two threshold values

after the 5 minute purge occurs, the thermostat will

activate a second 5 minute purge to double check the

water temperature. If after the second 5 minute purge,

the water temperature is still between the two thresholds,

the valve output will be disabled and only manual fan will

be available. It will stay in this operation until the next

purge cycle occurs.

2 Pipes with Auxiliary Heat

For this application, when there is hot water in the pipes,

the system switch provides "Off" and "Heat". When there

is cold water in the pipes, the system switch provides

"Off", "Heat", and "Cool".

Operation:

After exiting the installer setup, the thermostat will perform

a 5 minute purge. During this time, the valve (W/Y) will

energize and the fan and auxiliary heat (Y/A) will be de-

energized. After the 5 minute purge, the thermostat will

go into the appropriate mode as described by Table 7.

Table 7. Logic for 2 Pipes with Auxiliary Heat

If pipe temperature is between the two threshold values

after the 5 minute purge occurs, the thermostat will

activate a second 5 minute purge to double check the

water temperature. If after the second 5 minute purge,

the water temperature is still between the two thresholds,

the valve output will be disabled and only auxiliary heat

will be available for heating.

Auxiliary heat (Y/A) always de-energizes during purges.

Purge Cycles for 2 Pipe Seasonal Changeover

Applications

For 2 Pipe with Auto Changeover and 2 Pipe with

Auxiliary Heat applications, the thermostat will run purge

cycles to determine if there is hot or cold water in the

pipes.

A 5 minute purge will occur every 2 hours to ensure that

the pipe sensor is sensing the correct mode during

seasonal changeover months.

A 5 minute purge will also occur anytime the installer

setup or installer test menus are exited, whenever the

thermostat is switched from its "Off" position

1

, and if the

power is reset.

4 PIPES AUTO CHANGEOVER

Single Set Point Method

In 4 pipe auto changeover with a single setpoint, the

temperature is always controlled to the setpoint.

Switching points are used to determine when to switch

between heating and cooling modes. If the current mode

is heat and the temperature drifts above the cool switch

point (Setpoint + Switching Differential), the thermostat

will switch to heat operation and will heat the space until

setpoint is reached.

For this application, the setpoint setting and switching

points are illustrated in Fig. 29. The switching differential

is defined via IS code #10.

1

For the 2 Pipe with Auxiliary Heat application, the thermostat must be in the "Off" position for more than 30 minutes

before a 5 minute purge will occur when it is switched back into "Heat" or "Cool".

Pipe Temperature after purge

System Mode

>Threshold for Heating (IS code #7)

Heat

Between Thresholds

After Purge Occurs

Fan Only*

< Threshold for Cooling (IS code #6) Cool

Pipe

Temperature

After Purge

Heat Mode

Cool Mode

> Threshold

for Heating

(IS code #7)

Valve (W/Y)

energized on calls

for heat

Changeover.

Mode changes to

Heat.

Between

Thresholds

After Purge

Occurs

Aux Heat (Y/A)

energized on calls

for heat

Changeover. Mode

changes to Heat

because Cool is not

available.

< Threshold

for Cooling

(IS code #6)

Mode stays in Heat

but Aux Heat (Y/A)

energized on calls

for heat

Valve (W/Y)

energized on calls

for cool