TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS

62-0278—07

10

Fig. 21. Removing the thermostat.

SETUP

The thermostat provides an LCD display, two buttons

below the display for System and Fan control and two

adjustment buttons (Up and Down) to the right of the

display. See Fig. 23.

Settings, including setpoints, are permanently retained in

EEPROM in case of a power outage.

Fig. 22 illustrates all the possible LCD display elements.

Only those elements pertinent to the current settings and

status (including the text for the two buttons, System and

Fan), actually display.

Fig. 22. LCD display with all possible elements

shown.

Fig. 23. LCD display showing default screen.

Power-up

At power-up, the thermostat’s LCD shows all display

segments for two seconds, enters a self-test mode for a

few seconds, and then displays the current room

temperature (default screen), as shown in Fig. 23.

NOTE: If there is a temperature sensor failure or the

temperature is outside of the operating

range, the room temperature display shows

two dashes,

.

When the sensor returns to its operating

range, the temperature display resumes.

CAUTION

Equipment damage hazard.

Power overload will damage the thermostat.

The thermostat has a safety fuse rated at 15 A/

250 Vac. If the fuse blows, the thermostat must be

replaced. The fuse is not field replaceable.

This fuse is provided as a safety feature to prevent

fire if the thermostat is overloaded.

Installer Setup (IS) Mode

To enter Installer Setup Mode:

• Press and hold both the System button (labeled

Heat/Cool) and the Up Arrow button for three (3)

seconds.

This displays the setup screen on the LCD. See Fig. 24.

NOTE: Exiting Installer Setup Mode is the same as

the method for entering setup mode.

Table 4 provides the setup codes (IS codes) and values.

To enter the setup parameters:

1. Press the System (Heat/Cool) button to cycle

through the IS codes, which display in the upper

right following the word Setup.

2. Press the Up or Down Arrow buttons to cycle

through the option values for the currently displayed

IS code. The values display in the center of the

screen.

3. After the desired value displays, press the System

button to store your value selection and display the

next IS code.

M27592

M27584

Locked

Freeze Set to

Protect Setup

Set to RoomTemp

Test

Pipe

Sensor

Heat On Cool On

OffHeatAutoCool

LowMedHiAuto

Fan On

Economy

Setback

ºF ºC

ºF ºC

System

Fan

M27586

Set to

RoomTemp

Heat On

Heat

Auto

Fan On

ºF

ºF

UP AND DOWN

ARROW BUTTONS

SYSTEM

BUTTON

FAN

BUTTON