Chapter 4 WIRING AND CONNECTION

Figure 4-2 Terminal wiring

H

O

L

SJ-FB

(Feed-back board)

Inverter main body control

Configure to an

intelligent input term. 1-8

EP5

EG5
EAP
EAN
EBP
EBN
EZP
EZN

M

EC

Motor with

encoder

SAP
SAN
SBP
SBN

Pulse train pos.

command

POK Positioning completion signal

ZS Zero speed signal

DSE Speed deviation excessive signal

Output

terminal

FW

RV

LAC LAD cancellation signal

PCLR Position deviation Clear signal

ORT Orientation signal

CM1

Input

terminal

Configure to an

intelligent output term. 1-5

AP
AN
BP
BN

Encoder

signal output

STATPulse train input permisive signal

Encoder signal

TM1

TM2


4.3 Terminal Connections

(Note 1) : Please refer to the SJ300 Instruction Manual for information about wiring the logic

terminals.

(Note 2) : Use a shielded, twisted pair cable for the signal cables, and cut the shielded covering as

shown in the diagram below. Make sure that the length of the signal cable is no more
than 20 meters. If the length exceeds 20 meters, use a VX application control device
RCD-E (remote control device) or CVD-E (signal isolation) to avoid malfunction
caused by EMC noise or voltage drop. Also, the signal wire for the encoder should be
shielded twisted pair line of 28 AWG (0.75mm

2)

or more, and the distance should also

be less than 20m. If more than 20m, use a 5V line driver relay amplifier.


DO NOT GROUND

THIS END

Connect to common terminal
of the option board.

Insulation