1 action selection in case of option error, 3 warning display (feed back option relation) – Hitachi SJ-FB User Manual

Page 33

Advertising
background image

33

Chapter 8 PROTECTION FUNCTION

8.1 Action selection in case of option error

To ignore or make inverter trip can be selected in case of option error.

Item Function

code

Data

Contents

00

TRP: Inverter trips and outputs alarm signal.

Action selection in

case of option error

P001 / P002

01

RUN: Inverter ignores the option error and

continues the operation.

(Note) : Inverter trips anyway in case of encoder line break error (E60, E70), SJ-FB abnormal

connection (E69,E79) occurs, although action selection is set to 01 (RUN). Please refer to
"Chapter 5.2 FEED-BACK BOARD INITIAL SETTINGS".

8.2 Causes and Countermeasures for Option Board Errors

When any of the following alarms occurs, the inverter displays the alarm cause and stops.

Display

Item

Contents

Processing

Detect the line break or disconnection of the
encoder line.

Check the encoder signal line and
connection.

Detect when there is an encoder failure.
Detect when the specification of the encoder is
not line driver output type.

Replace it to a suitable one.

E60

(E70)

(Note 1)

Encoder line

break

Detect when there is no Z pulse.

Turn SWENC-2 OFF on the option
board.

E61

(E71)

(Note 1)

Over speed

Detect when the motor rotation speed exceeds
(maximum frequency (note 2))

×(over speed

error detection level (P026).
(Note 3),(Note 4)

Adjust the Kp and J constants
related to the speed control system
to reduce overshoot.

E62

(E72)

(Note 1)

Positioning

error

Detect when the deviation of the current
position and command value becomes more
than 1,000,000 pulses during position
controlling.

Increase the position loop gain.
Decrease the numbers of the pulse
train input per second.

E69

(E79)

(Note 1)

connection

error

Detect abnormal connection between the
inverter main body and SJ-FB.

Check the connection between the
inverter main body and SJ-FB.

(Note 1): Data in parentheses ( ) applies when the option card is connected to option slot 2.
(Note 2): Frequency upper limit value (A061/A261) is reflected when it is set.
(Note 3): It depends on what type of main body combines with the SJ-FB, the setting value
conversion is different.
Please refer to the (Note 3) of the “5.3 Items regarding the feed back board of the
inverter main body“.
(Note 4): When the over speed error occurred . There is a possibility the over speed error occur

again. Even though the trip is cleared during the motor free run. In this case stop the
motor, then clear the trip please.


8.3 Warning display (Feed back option relation)

(Refer to the operation manual of the main body about the warning other than the following,)

The 009 is displayed in the case that it became orientation speed setting (P015) > the highest

Advertising