Chapter 4 WIRING AND CONNECTION




(Note 3) : Be sure to separate the power wiring from the control circuit wiring. If they have to be

crossed, be sure that they cross at a right angle.

Power cables

R, S, T, U, V, W, P, PD,

RB, N, R0, T0 etc.

Right angle

Input/Output signal lines

Control signals (STAT, ORT, LAC, PCLR, SAP, SAN, SBP, SBN,
EAP, EAN, EBP, EBN, POK, DSE, ZS, AP, AN, BP, BN, L, EP5,
EG5, CM1, CM2, P24, PLC etc.)

Separate 10cm or more.


(Note 4) : Take care not to short circuit between the EP5 and EG5 terminals. There is a danger of

malfunction.

(Note 5) : Isolate common signal for inverter analog signals (L terminal of the logic card of

SJ300) from common terminal of the SJ-FB.

(Note 6) : Be sure to connect the encoder signal lines properly so that the relationship among their

phases is as shown below during rotation of the motor (Standard EG5).

15

EAP

EAN

EBP

EBN

EZP

EZN