Hitachi SJ-FB User Manual

Page 17

Advertising
background image

17

Chapter 5 SETTING

5.3 Inverter Configuration Parameters for the SJ-FB Board

Code

Function name

Setting range

Initial data

Setting

on run

Change

mode on

run

A044 1

st

control method

00(VC) / 01(VP1.7power) / 02(Free V/f Setting)

/ 03(SLV) / 04(0Hz area SLV) / 05(V2)

00 -

-

H001

Auto-tuning mode
selection

00(NOR : Invalid) / 01(NRT : not rotate)/ 02(AUT :

rotate)

00 -

-

H002

1

st

motor constant

selection

00(Hitachi standard motor constant)/
01(Auto-tuning data)/
02(Auto tuning data with online auto-tuning)

00 -

-

H003

1

st

motor capacity

selection

0.20 - 75.0(kW)

Setting on

forwarding

- -

H004

1

st

motor pole

selection

2/4/6/8 (Poles)

4

-

-

H005

1

st

motor speed

response setting

0.001 - 9.999 / 10.00 - 65.53

1.590

H006 1

st

stabilized factor

0. - 255.

100.

H020 1

st

motor R1 setting

0.000 - 9.999 / 10.00 - 65.53(

Ω)

depends on

the motor

capacity

- -

H021 1

st

motor R2 setting

0.000 - 9.999 / 10.00 - 65.53(

Ω)

depends on

the motor

capacity

- -

H022 1

st

motor L setting

0.00 - 99.99 / 100.0 - 655.35(mH)

depends on

the motor

capacity

- -

H023 1

st

motor I

0

setting

0.00 - 99.99 / 100.0 - 655.35(A)

depends on

the motor

capacity

- -

H024 1

st

motor J setting

0.000 - 9.999 / 10.00 - 99.99 /

100.0 - 9999.(kgm

2

)

depends on

the motor

capacity

- -

H030

1

st

motor R1 setting

(Auto-tuning data)

0.000 - 9.999 / 10.00 - 65.53(

Ω)

depends on

the motor

capacity

- -

H031

1

st

motor R2 setting

(Auto-tuning data)

0.000 - 9.999 / 10.00 - 65.53(

Ω)

depends on

the motor

capacity

- -

H032

1

st

motor L setting

(Auto-tuning data)

0.00 - 99.99 / 100.0 - 655.35(mH)

depends on

the motor

capacity

- -

H033

1

st

motor I

0

setting

(Auto-tuning data)

0.00 - 99.99 / 100.0 - 655.35(A)

depends on

the motor

capacity

- -

Advertising