3 control cable connections – crs-300 to modems – Mocomtech CRS-300 User Manual

Page 111

Advertising
background image

CRS-300 1:10 Redundancy Switch

Revision 16

Cables and Connections

MN/CRS300.IOM

4–51

2. The Traffic CDM-700 must have the same interface cards in each slot as any of the other

Traffic CDM-700s have, or a blank panel installed.

3. OC3 Optical TMI is not currently available.
4. As of April 2007:

• CRS-336 TMI card replaces the CRS-335.
• CRS-306 RMI card replaces the CRS-305.

4.7.3

Control Cable Connections – CRS-300 to Modems

The Control Cable CA/WR12361-1 provides the serial communication path between the Switch
and the modems and controls the modem’s external Tx IF-mute control line, and is therefore
always required.

Refer to Figure 4-22 and Figure 4-23 to connect and secure the CA/WR12361-1 cables
between the CRS-300 and each CDM-700 as follows:

HD-15F connector labeled “J1” on the RMI or TMI(s), to

DB-15M connector labeled “P1 Alarms” on the CDM-700.

4.7.4

Serial Traffic Data Connections – CRS-300 to Modems

If G.703 is the traffic data type

, refer to Figure 4-22, Figure 4-23, Figure 4-25, or Figure

4-27

to connect and secure the Traffic Data Cables CA/RF12278-1 and CA/RF12279-1 the CRS-

300 and each CDM-700 as follows:

First

, connect and secure the CA/RF12279-1 cable between the Redundant CDM-700 and the

CRS-300:

DB-15M connector labeled “P1” on the RMI, to

BNC connectors (<4X> per installed CDI-10 card) on the Redundant CDM-700
(depending on the modem configuration, either <4X> or<8X> BNC connectors are used).

Next

, connect and secure the CA/RF12278-1 cables between the CRS-300 and the Traffic

CDM-700(s):

DB-9M connector labeled “P1” on the TMI(s), to

BNC connectors (4X per installed CDI-10 card) on each Traffic CDM-700
(depending on the modem configuration, either <4X> or <8X> BNC connectors are used).

If HSSI is the traffic data type

, refer to Figure 4-23 and Figure 4-26 to connect and secure the

HSSI Data Cable CA/WR9189-6 between the CRS-300 and each CDM-700 as follows:

HSSI (HD-50F) connector labeled “J2” on the RMI, or “J3” on the TMI(s), to

HSSI (HD-50F) connector labeled “HSSI” on each CDM-700.

If OC3 copper is the traffic data type

, refer to Figure 4-24 to connect and secure the pair of

BNC PL/0813-8 cables between the CRS-300 and each CDM-700 as follows:

• BNC connectors labeled "J4 Tx" on the RMI, or "J3 Tx"on the TMI(s), to BNC

connectors labeled "Tx" on the CDM-700's CDI-50 interface card, and

• BNC connectors labeled "J3 Rx" on the RMI, or "J5 Rx"on the TMI(s), to BNC

connectors labeled "Rx" on the CDM-700's CDI-50 interface card.