Mocomtech CRS-300 User Manual

Page 46

Advertising
background image

CRS-300 1:10 Redundancy Switch

Revision 16

Installation

MN/CRS300.IOM

2–2

or on top of the rack. If using the CRS-280L, refer also to the associated CRS-280L 1:N
Redundancy Switch Installation and Operation Manual
(MN/CRS280L.IOM) for further rack
mounting information. The CRS-350 mounts to the back of the rack. The mounting hardware
allows the user to hinge the unit down to access the data cables in the rear of the unit to connect
the cables to the modems. Mount all Switches and modems in the rack as necessary.

IMPORTANT

Do not allow the internal rack temperature to exceed 50°C (122° F).

It is important to ensure that there is adequate clearance for ventilation in the rack. Since the
Switch itself is relatively passive, no additional clearance is needed between it and the nearest
modem. In rack systems where there is high heat dissipation, provide forced-air cooling by
installing top- or bottom-mounted fans or blowers.



Figure 2-1. Typical Rack Mounting Configuration