Milwaukee LSM40MP-2 User Manual

Page 16

Advertising
background image

16

NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

Figure 27 - Top Vent - THREE ELBOWS

V

H1

H

V1

Ceiling

Firestop/Spacer

(SV8BF)

Wall

Firestop/Spacer

(SV8HF)

Table B

H + H1 Maximum

V Minimum

feet

(meter)

feet

(meter)

10

(3.1)

2.5

(0.762)

15

(4.65)

3.5

(1.06)

20

(6.2)

4.5

(1.37)

H + H1 = 20 feet (6.2 m) Max.

V + V1 + H + H1 = 40 ft. (12.4 m) Max.

V + V1 = 11 feet (3.3 meters) Min. for LSM40-2

V + V1 = 10.5 feet (3.2 meters) Min. for LSM45-2

H

V

V1

Ceiling

Firestop/Spacer

(SV8BF)

Table A

H Maximum

V Minimum

feet

(meter)

feet

(meter)

10

(3.1)

2.5

(0.762)

15

(4.65)

3.5

(1.07)

20

(6.2)

4.5

(1.37)

V + V

1

+ H = 40 feet (12.4 meters) Max.

V + V

1

= 11 feet (3.3 meters) Minimum for LSM40-2

V + V

1

= 10.5 feet (3.2 meters) Minimum for LSM45-2

Figure 26

- Top Vent - Corner Framing with Square Termination (SV8HTS)

TWO 90 DEGREE ELBOWS

40 feet (12.2 meters)

Maximum

6 feet (1.8 meters)

Minimum

Ceiling

Firestop/Spacer

(SV8BF)

Figure 25

- Top Vent - STRAIGHT

VERTICAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ (rigid vent pipe) is shown

in the Figures.

• It is very important that the horizontal/in-

clined run be maintained in a straight (no

dips) and recommended to be in a slightly

elevated plane, in a direction away from the

fireplace of 1/4" rise per foot (20 mm per

meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all

the way down to at or near level.

SV8BF (Secure Vent) firestop/spacer must

be used anytime vent pipe passes through a

combustible floor or ceiling. SV8HF (Secure

Vent) firestop/spacer must be used anytime

vent pipe passes through a combustible

wall.

Two 45 degree elbows may be used in place

of one 90 degree elbow. The same rise to

run ratios, as shown in the venting figures

for 90 elbows, must be followed if 45 degree

elbows are used.

A Vent Restrictor, as shown in Figure 15 on Page

12, may need to be used in this application

Example: If 20 feet of (H)

horizontal vent run is needed,

then 4-1/2 feet minimum of (V)

vertical vent will be required.

Example: If 20 feet of (H+ H

1

) horizon-

tal vent run is needed, then 4-1/2 feet

minimum of (V) vertical vent will be

required.