NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

3"

(76 mm)

Termination Kit

Combustible Projection

greater than 2-1/2 inches in length

Horizontal Vent Termination Clearances

Combustible Projection

2-1/2 inches or less in length

24"

(610 mm)

Ventilated Or

Unventilated Soffit

Figure 6 - Side Elevation View

See Figure 30 on Page 18 for the recess allowances, into

exterior walls, of the square horizontal terminations.

Termination Heights For Vents

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1

Roof Pitch

* Feet

* Meters

Flat.to.6/12

1.0

0.3

6/12.to.7/12

1.25

0.38

7/12.to.8/12

1.5

0.46

8/12.to.9/12

2.0

0.61

9/12.to.10/12

2.5

0.76

10/12.to.11/12

3.25

0.99

11/12.to.12/12

4.0

1.22

12/12.to.14/12

5.0

1.52

14/12.to.16/12

6.0

1.83

16/12.to.18/12

7.0

2.13

18/12.to.20/12

7.5

2.29

20/12.to.21/12

8.0

2.44

The.vent./.air.intake.termination.clearances.

above.the.high.side.of.an.angled.roof.is.as.

shown.in.the.following.chart:

12

x

Roof Pitch is x/12

2 FT

MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum

Clearance to Combustibles

Vertical Vent Termination Clearances

Figure 5

VENT TERMINATION CLEARANCES

These instructions should be used as a

guideline and do not supersede local codes

in any way. Install vent according to local

codes, these instructions, the current National

Fuel Gas Code (ANSI-Z223.1) in the USA or

the current standards of CAN/CSA-B149.1 in

Canada.

Vertical Vent Termination Clearances

Terminate.multiple.vent.terminations.according.

to.the.installation.codes.listed.above..Also.see.

Figure 4.

Terminate.single..vent.caps.relative.to.building.

components.according.to.Figure 5.

Horizontal Vent Termination Clearances

The.horizontal.vent.termination.must.have.a.minimum.of.3".(76.mm).clearance.to.any.overhead.

combustible.projection.of.2-1/2".(64.mm).or.less.(see..

Figure 6). .For.projections.exceeding.2-1/2"..

(64.mm),.see.

Figure 7..For.additional.vent.location.restrictions.refer.to.Figure 7 on Page 7.

12”

(305mm)

Minimum

Figure 4 - Multiple Terminations