NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

17

Vertical

Rise

SV8E90

Elbow

Horizontal / Inclined Run

SV8HTS

Termination

Shown

Firestop/Spacer

SV8 L6/12/24/36/48

Vent Sections

Support Bracket Spacing

Every 3 ft (914 mm)

SV8HTS

Termination

Shown

Support

Brackets

Building

Support

Framing

Ceiling

Fireplace

Exterior

Wall

Exterior

Wall

TYPICAL HORIZONTAL VENT INSTALLATION

2-1/2 Foot Vertical

Vent (min.)

Figure 28

Support the vertical portion of the venting system

every 8 feet (2.4m) above the fireplace vent outlet.

Push. the. vent. component. against. the. collar.

until.it.fully.engages,.then.twist.the.component.

clockwise,.running.the.dimples.down.and.along.

the.incline.channels.until.they.seat.at.the.end.

of. the. channels.. . The. unitized. design. of. the.

Secure Vent.components.will.engage.and.seal.

both.the.inner.and.outer.pipe.elements.with.the.

same.procedure...Sealant.and.securing.screws.

are.not.required.

E. Attach vent components to each other -.Other.

vent.sections.may.be.added.to.the.previously.

installed.section.in.accordance.with.the.require-

ments.of.the.vent.tables...To.add.another.vent.

component.to.a.length.of.vent.run,.align.the.

dimpled.end.of.the.component.over.the.inclined.

channel.end.of.the.previously.installed.section,.

adjusting.the.radial.alignment.until.the.four.lock-

ing.dimples.are.aligned.with.the.inlets.of.the.four.

incline.channels.of.the.previous.section...Push.

the.vent.component.against.the.previous.section.

until.it.fully.engages,.then.twist.the.component.

clockwise.running.the.dimples.down.and.along.

the.incline.channels.until.they.seat.at.the.end.of.

the.channels..This seating position is indicated

by the alignment of the arrow and dimple as

shown in.Figure 19 on Page 14.

F..Install firestop/spacer at ceiling -

When.using.

Secure Vent,.use.SV8BF.firestop/

spacer.at.ceiling.joists..If.there.is.living.space.

above.the.ceiling.level,.the.firestop/.spacer.must.

be.installed.on.the.bottom.side.of.the.ceiling..

If.attic.space.is.above.the.ceiling,.the.firestop/.

spacer. must. be. installed. on. the. top. side. of.

the.joist...Route.the.vent.sections.through.the.

framed.opening.and.secure.the.firestop/spacer.

with.8d.nails.or.other.appropriate.fasteners.at.

each.corner.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections.

G..Support the vertical run sections -

See.

Section E.on Page 14.

H. Change vent direction - .At.transition.from.or.

to.a.horizontal/inclined.run,.install.the.SV8E45.

and.SV8E90.elbows.in.the.same.manner.as.the.

straight.vent.sections...The.elbows.feature.a.twist.

section.to.allow.them.to.be.routed.about.the.

center.axis.of.their.initial.collar.section.to.align.

with.the.required.direction.of.the.next.vent.run.

element..Twist elbow sections in a clockwise

direction only so as to avoid the possibility of

unlocking any of the previously connected vent

sections (see.Figure 19 on Page 14).

I..Continue installation of horizontal/inclined

sections -..Continue.with.the.installation.of.the.

straight.vent.sections.in.horizontal/inclined.run.

as.described.in.

Step E..Install.support.straps.

every.3.feet.(1914.mm).along.horizontal/inclined.

vent.runs.using.conventional.plumber’s.tape..

See.

Figure 28,.it is very important that the

horizontal/inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal,.though.rise.per.foot.

run.ratios.that.are.smaller.are.acceptable.all.the.

way.down.to.at.or.near.level...

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the top,

1" (25 mm) at sides, and 1" (25 mm) at the

bottom for all horizontal/inclined runs.

Use. a. carpenter’s. level. to. measure. from. a.

constant.surface.and.adjust.the.support.straps.

as.necessary..

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM

See.

Figures 28, 31, 32 and 33 on Pages 17,

19 and 20 and.their.associated.Horizontal.Vent.

Table. which. illustrate. the. various. horizontal.

venting. configurations. that. are. possible. for.

use. with. these. appliances.. .

Secure Vent™.

pipe.applications.are.shown.in.these.Figures...

A. Horizontal. Vent. Table. summarizes. each.

system’s.minimum.and.maximum.vertical.and.

horizontal. length. values. that. can. be. used. to.

design. and. install. the. vent. components. in. a.

variety.of.applications..

The.horizontal.vent.system.terminates.through.

an.outside.wall..Building.Codes.limit.or.prohibit.

terminating.in.specific.areas..Refer.to.Figure 7

on Page 7.for.location.guidelines.

Secure Vent.SV8.direct-vent.system.compo-

nents.are.unitized.concentric.pipe.components.

featuring.positive.twist.lock.connection,.(refer

to Figure 19.on Page 14)...All.of.the.appli-

ances.covered.in.this.document.are.fitted.with.

collars.having.locking.inclined.channels..The.

dimpled.end.of.the.vent.components.fit.over.

the.appliance.collar.to.create.the.positive.twist.

lock.connection.

A..Plan the vent run -.

Analyze.the.vent.routing.and.determine.the.

types. and. quantities. of. sections. required.......

4-1/2".(114.mm),.10-1/2".(267.mm),.22-1/2".

(572.mm),.34-1/2".(876.mm).and.46-1/2".(1181.

mm). net. section. lengths. are. available.. . It. is.

recommended.that.you.plan.the.vent.lengths.

so.that.a.joint.does.not.occur.at.the.intersection.

of.ceiling.or.roof.joists..Make.allowances.for.

elbows.as.indicated.in.Figure 21 on Page 15..

Maintain a minimum 1" (25 mm) clearance

to combustibles on the vertical sections.

Clearances for the horizontal runs are; 3"

(76 mm) on top, 1" (25 mm) on sides, and

1" (25 mm) at the bottom.

B..Frame exterior wall opening -.

Locate. the. center. of. the. vent. outlet. on.

the. exterior. wall. according. to. the. dimen-

sions. shown. in.

Figure 12 on Page 10...

Cut. and/or. frame. an. opening,. 15". x. 13"..

(381.mm.x.330.mm).inside.dimensions,.with.

9".above.center.and.7".below.center.

C.. Frame ceiling opening -. If. the. vertical.

route.is.to.penetrate.a.ceiling,.use.plumb.line.

to.locate.the.center.above.the.appliance..Cut.

and/or.frame.an.opening,.13".x.13".(330.mm.x.

330.mm).inside.dimensions,.about.this.center.

(refer.to.Figure 18 on Page 14).

D. Attach vent components to appliance - To.

attach.a.vent.component.to.the.appliance.collar,.

align.the.dimpled.end.over.the.collar,.adjust-

ing.the.radial.alignment.until.the.four.locking.

dimples.are.aligned.with.the.inlets.of.the.four.

incline.channels.on.the.collar.(refer to Figure

19..on Page 14).