NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

19

H

V

Wall Firestop/Spacer

(SV8HF)

Ceiling

Firestop/Spacer

(SV8BF)

Table C

H Maximum

V Minimum

feet

(meter)

feet

(meter)

3.5

(1.07)

2.5

(0.762)

6.5

(1.98)

3.5

(1.07)

8.5

(2.6)

4.5

(1.37)

10.5

(3.2)

5.5

(1.68)

12.5

(3.8)

6.5

(1.98)

14.5

(4.4)

7.5

(2.3)

16.5

(5.0)

8.5

(2.6)

18.5

(5.6)

9.5

(2.9)

20

(6.0)

10

(3.0)

V + H = 40 feet (12.4 m) Max.

H = 20 ft. (6.2 m) Max.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV8HTS)

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination.Kit.Only

5.to.8-1/2.(127.to.216)

Termination.Kit.and..6.In..Vent.

Section.(SV8L6)

9-3/4.to.14.(248.to.356)

Termination. Kit. and. Tele-

scopic.Section.(SV8LA)

6-3/4.to.15-1/4.(171.to.387)

Termination. Kit. and. Tele-

scopic.Section.(SV8LA).and.6.

in..vent.section.(SV8L6)

11-1/4.to.19-3/4.(286.to.502)

Table 8

See Table 8 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

Example: If 20 feet of (H) hori-

zontal vent run is needed, then

10 feet minimum of (V) vertical

vent will be required.

HORIZONTAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ components (rigid vent pipe and terminal) are shown

in the Figures.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting figures for 90

elbows, must be followed if 45 degree elbows are used.

SV8BF (Secure Vent) firestop/spacer must be used anytime vent pipe

passes through a combustible floor or ceiling. SV8HF (Secure Vent)

firestop/spacer must be used anytime vent pipe passes through a

combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

Figure 31

-

Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

See.Table 8..as.an.aid.in.venting.component.selection.for.

a.particular.range.of.exterior.wall.thicknesses.

Square termination (SV8HTS) shown.