Recommended Branch Circuit Protection Devices

Branch circuit protection must be installed on the input (line side) of the drive controllers. Input fuses
may be used on 1/2 hp to 500 hp drive controllers; circuit breakers may be used on 1/2 hp to 100 hp
drive controllers.

Fuses

The fuses specified in Tables 1–3 (pages 113–114) are suitable for branch short circuit protection and
provide excellent short circuit protection for the drive. Fuses are recommended for ATV58 TRX Type H
and Type FVC drives when they are wall mounted.

Circuit Breakers

Circuit breakers will also provide branch short circuit protection. Because circuit breakers are typically
slower than fuses, they are not as effective in limiting damage to the controller in the event of an internal
drive short circuit such as shorted bus connections, shorted input rectifier, or failure of the internal solid
state overcurrent protection circuit in the controller. Refer to the ALTIVAR 58 TRX Installation Guide for
Type H Controllers (VVDED397048US) for recommended circuit breakers and application
considerations.

Table 1: Recommended Fuses: 208/230 V Single-Phase Drive Controllers

Motor

Drive Controller

F1-F2

Line Power Fuses

hp

kW

ATV58H•••••

Class J

0.5

0.37

U09M2

10

[1]

1

0.75

U18M2

15

[1]

2

1.5

U29M2

30

[1]

3

2.2

U41M2

30

[1]

4

3

U72M2

35

[1]

5

4

U90M2

60

[1]

7.5

5.5

D12M2

70

[1]

10

7.5

D16M2

90

[2]

15

11

D23M2

125

[2]

20

15

D28M2

150

[2]

25

18.5

D33M2

175

[2]

30

22

D46M2

200

[2]

Table 2: Recommended Fuses: 208/230 V Three-Phase Drive Controllers

Motor

Drive Controller

F1-F2-F3

Line Power Fuses

hp

kW

ATV58H•••••

Class J

[1]

2

1.5

U29M2

15

3

2.2

U41M2

20

3

U54M2

30

5

4

U72M2

35

7.5

5.5

U90M2

60

10

7.5

D12M2

70

hp

kW

CTLN

ATV58H•••••

F1-F2-F3

Class J

[2]

CT, VTLN
ATV58H••

•••

F1-F2-

F3

Class J

[2]

VT

ATV58H••

•••

F1-F2-F3

Class J

[2]

10

7.5

D16M2

70

15

11

D23M2

90

D16M2

70

D16M2

70

20

15

D28M2

110

D23M2

90

D16M2

90

25

18.5

D33M2

125

D28M2

110

D23M2

125

30

22

D46M2

175

D33M2

125

D28M2

150

40

30

D46M2

175

D33M2

175

50

37

D46M2

200

[1] Fast-acting or time
delay Class J fuses are
acceptable. Class T
fuses are acceptable.
Class CC fuses may be
used if recommended
fuse rating is 30 A or
lower.

[2] Fast-acting Class J
fuses. Class T fuses are
acceptable.

[1] Fast-acting or time
delay Class J fuses are
acceptable. Class T
fuses are acceptable.
Class CC fuses may be
used if recommended
fuse rating is 30 A or
lower.

[2] Fast-acting Class J
fuses. Class T fuses are
acceptable.

CT

Constant Torque

CTLN

Constant Torque Low
Noise

VTLN

Variable Torque Low
Noise

VT

Variable Torque