Gas Requirements

70256801

34

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Turn on gas and check all pipe connections (internal

and external) for gas leaks with a non-corrosive leak

detection fluid. Purge air in gas service line by

operating the tumblers in the drying mode. If burner

does not light and unit goes into lockout, open and

close the door and restart. Repeat these steps until

burner ignites. Use pipe compound, resistant to
actions of L.P. Gas, on all pipe threads.

Figure 13

WARNING

Do not use an open flame to check for gas
leaks! To reduce the risk of explosion or
fire check all pipe connections, internal
and external, for gas leaks using a non-
corrosive leak detection fluid. Check gas
connections annually for leakage.

W408

T135I

1

Gas Line to Tumbler

2

1/8 in. NPT Plug

3

Gas Supply Piping System

4

Gas “T” Fitting

5

6 in. (152 mm) Minimum Gas Pipe

6

Gas Pipe Cap

7

Dirt and Water Vapor Trap

8

Shut-Off Valve

T378I

1

2

3

4

5

6

7

8