50 pound tumbler electrical requirements, Table 12 – Speed Queen Drying Tumblers none User Manual

Page 46

Advertising
background image

Electrical Requirements

70256801

44

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

50 Pound Tumbler Electrical
Requirements

Refer to Table 12.

NOTE: Minimum wire sizes are obtained from the
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.

NOTE: Use copper conductors only.

NOTE: Connect to individual branch circuit.

Table 12

Heat Source

Serial Plate Voltage

Terminal Block

Connections

Required

Rated

Current

Breaker

Rating

Breaker

Poles

Recommended

Wire Size

Gas and Steam 120 Volt/60 Hertz/

1 Phase

L1, Neutral and ground

*

20 Amps

1

12 AWG

(3.9 mm

2

)

Gas and Steam 208 or 240 Volt/

60 Hertz/1 Phase

L1, L2, Neutral and
ground

*

15 Amps

2

14 AWG

(2.6 mm

2

)

Gas and Steam 230-240 Volt/50 Hertz/

1 Phase

L1, Neutral and ground†

*

15 Amps

1

14 AWG

(2.6 mm

2

)

Gas and Steam 208 or 240 Volt/

60 Hertz/3 Phase

L1, L2, L3, and ground†

*

15 Amps

3

14 AWG

(2.6 mm

2

)

Gas and Steam 380 or 415 Volt/

50 Hertz/3 Phase

L1, L2, L3 and ground

*

15 Amps

3

14 AWG

(2.6 mm

2

)

Gas and Steam 460-480 Volt/60 Hertz/

3 Phase

L1, L2, L3 and ground

*

15 Amps

3

14 AWG

(2.6 mm

2

)

Electric

240 Volt/50 Hertz/

1 Phase

L1, Neutral and ground

91 Amps

100 Amps

1

2 AWG

(43 mm

2

)

Electric

208 Volt/60 Hertz/

3 Phase

L1, L2, L3 and ground

88 Amps

100 Amps

3

2 AWG

(43 mm

2

)

Electric

240 Volt/60 Hertz/

3 Phase

L1, L2, L3 and ground

78 Amps

90 Amps

3

2 AWG

(43 mm

2

)

Electric

240 Volt/50 Hertz/

3 Phase

L1, L2, L3 and ground

78 Amps

90 Amps

3

2 AWG

(27 mm

2

)

Electric

380 Volt/50 Hertz/

3 Phase

L1, L2, L3 and ground† 50 Amps

60 Amps

3

4 AWG

(27 mm

2

)

Electric

415 Volt/60 Hertz/

3 Phase

L1, L2, L3, and ground† 46 Amps

60 Amps

3

4 AWG

(27 mm

2

)

Electric

480 Volt/60 Hertz/

3 Phase

L1, L2, L3, and ground

38 Amps

50 Amps

3

6 AWG

(17 mm

2

)

*Current Ratings vary slightly depending on model; refer to serial plate.
†MT (manual timer)/CD (rotary coin drop) Models may require a Neutral conductor. Consult wiring diagram.