Power and Control Wiring

12

4.5

Power Supply

The STS2/PDU is supplied with redundant power supplies that are designed to operate from a voltage

range of 200V to 600V. The unit is set at the factory to match the nameplate voltage. Field adjust-

ments are not necessary. If the unit needs to operate at a voltage other than what is listed on the

nameplate, contact Liebert Global Services or your local Liebert representative. Table 6 provides

transformer tap information.
Table 6

Terminal block 1 and terminal block 2 wire connections

Voltage

Connect

Connect

Jumper Between

F1 TB1-XX

F2 TB1-YY

F3 TB2-XX

F4 TB2-YY

200

1

9

1

9

1-7

220

2

12

2

12

6-8

380

1

8

1

8

2-7

415

1

10

1

10

4-7

600

1

12

1

12

6-7

208

1

10

1

10

1-7

240

1

11

1

11

1-7

400

1

9

1

9

3-7

480

1

11

1

11

5-7

!

CAUTION

Using Table 6, ensure that the wiring for the control transformers matches the input voltage

for the unit.
Improper wiring could result in blown fuses.