Troubleshooting & repair – Lincoln Electric WELDANPOWER SVM 113-A User Manual

Page 60

Advertising
background image

MAIN STATOR TEST

(continued)

FIGURE F.6 - MAIN STATOR MOLEX PLUG TEST POINTS

FIGURE F.6

MAIN STATOR MOLEX PLUG TEST POINTS

FIGURE F.7

DIODE BRIDGE LEAD ASSIGNMENTS

5. Locate the 6 pin molex type connector

from the main stator.

6. Check for 240 - 260 VAC at leads #6A to

#3A. See Figure F.6. You may want to shut
off the engine, insert the test probes into
the molex plug, then restart the engine.
Cut any necessary cable ties to perform the
test.

NOTE: Insert the probes on the STATOR side

of the plug. This will eliminate the
possibility of problems in the plug
itself.

7. Check for 120 - 130 VAC at leads #5A to

#3A. See Figure F.6.

8. At the field rectifier diode bridge, check for

37.5 VAC at leads #9A (Brown) to #7A
(Blue). See Figure F.7 and the Wiring
Diagram. You may check these leads at
the molex plug; however, it's best to check
them at the rectifier bridge.

9. Check for 21.5 VAC at leads #9A (Brown)

to #15A (Yellow). See Figure F.6.

10. If any ONE of the voltage readings are

incorrect, the main stator may be faulty.

11. If ALL the voltage readings are incorrect,

the problem may be the engine RPM or
rotor field problems.

12. After the problem has been repaired,

replace any cable ties that were cut for the
test.

13. Install the control panel with the 6 sheet

metal screws. Use the 5/16" nut driver
and 5/16" wrench.

14. Replace the top cover on the control box.

Tighten the 8 sheet metal screws with the
5/16" nut driver.

TROUBLESHOOTING & REPAIR

F-22

F-22

WELDANPOWER 125

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

6A – Black

TO STATOR

7A (Blue)

201 (Black)

201C (Black)

9A (Brown)

200 (Red)

200C (Red)

9B (Brown)

+

5A – White

3A – Black

7A – Blue

15A – Yellow

9A – Brown