Liebert 30-130kVA User Manual

Page 83

Advertising
background image

Operation

75

Trap Fuse

Fail

Trap Fuse Fail

Fault

NO

YES

NO

YES

On units equipped with an input filter,

Control Logic has determined that one or

more of the filter fuses is open. The logic

will open the Input filter contactor. The UPS

will continue to run, without input filtering.

Contact Liebert Global Service to check

and repair the input filter.

On Battery

On Battery

Alarm

NO

NO

NO

YES

Reports an On Battery state as long as the

battery CB is closed, Input Undervoltage

alarm exists, and the status bit ON UPS is

set.

Battery

Overcharge

Battery

Overchg

Fault

YES

YES

NO

YES

Battery charge current is 50% above the

Battery Charge Current Limit for longer than

5 seconds. The load will be transferred to

Bypass. If Bypass is not available the UPS

will attempt to run from the battery. If both

battery and bypass are not available, a full

system shutdown will be initiated. This fault

will inhibit start-up. Contact Liebert Global

Services immediately

Byp Freq

Error

Bypass

Frequency

Error

Fault

NO

NO

NO

YES

The bypass frequency is outside the ± 5%

of the system rating. If the load is on

bypass the static switch will be shut down

and power will be lost to the load. If the load

is on UPS, transfer to bypass will be

inhibited, until this fault clears or is

corrected. This fault will inhibit startup. If

fault persists check the bypass source for

the cause of the frequency irregularity.

Contact Liebert Global services if you have

questions.

Byp ovld

Shutdown

Bypass

OverLoad

Shutdown

Fault

YES

YES

NO

YES

With the load on Static Bypass the system

has determined that at least one phase of

the Bypass has exceeded the KVA, KW, or

RMS current vs. Time overload spec. The

Static Bypass switch will be turned of and

the system will be shut down. Power to the

load will be turned off. Remove the excess

load from the UPS and attempt to re-start. If

the load is below the rating of the UPS and

it will not re-start, contact Liebert Global

Services.

Byp Phase

Rot Error

Bypass Phase

Rotation Error

Fault

NO

NO

NO

YES

The power conductors on the bypass line

are not wired to the UPS in the required

sequence. This alarm should appear only

during initial start-up or after a repair to the

source power system. Disconnect power

from the bypass line and correct the wiring.

Liebert Global Services must be present

during initial start-up of your UPS System.

IDC Peak

IDC Peak

Fault

YES

YES

NO

YES

The system has detected a failed IGBT.

The unit will transfer to Bypass if available.

Contact Liebert Global Services

immediately.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)