Liebert 30-130kVA User Manual

Page 95

Advertising
background image

Operation

87

Auto Restart

Failed

Auto Restart

Failed

Alarm

NO

NO

NO

YES

If Auto Restart feature is installed and

enabled, and the last shutdown was due to

a failed Batt Low Transfer, the Monitor will

automatically attempt to perform the

“normal” startup sequence when power is

reapplied to normal value. This alarm is

issued if the restart could not be performed

before the Auto Restart timeout expired.

The Monitor will abort the auto restart.

Auto Rexfer

Primed

Auto

Retransfer

Primed

Alarm

NO

NO

NO

YES

An automatic retransfer will be initiated

when the OK to Transfer condition has

been present for 10 seconds, if the

overload has dropped below 100% of the

rated load.

LBS Active

LBS Active

Alarm

NO

NO

NO

YES

The Load Bus Sync Option is active.

On Gen

Active

On Gen Active Alarm

NO

NO

NO

YES

A generator is supplying the system.

Load On UPS Load On UPS

Alarm

NO

NO

NO

YES

The Static Switch is off and the load is on

UPS. Momentary display. Sets flag in the

event history log.

Load On

Bypass

Load On

Bypass

Alarm

NO

NO

NO

YES

The critical load is being supplied power

from the bypass line, and is therefore

exposed to utility power disturbances. Clear

all of the alarms before attempting to

retransfer the load from the bypass line to

the UPS

Password

Entered

Password

Entered

Alarm

YES

NO

NO

YES

The User has modified the Password.

Momentary display. Sets flag in the event

history log.

Auto Restart

Init

Auto Restart

Initiated

Alarm

NO

NO

NO

YES

If the Auto Restart feature is installed and

enabled, and the last shutdown was due to

a failed Batt Low Txfer, the Monitor

automatically initiates the “normal” startup

sequence when the source power is

reapplied to normal value. This alarm is

issued as notification that auto-restart has

begun. No action required.

Normal

Operation

Normal

Operation

Alarm

NO

NO

NO

YES

Notification that no active alarms/faults

exist. Sets flag in the event history log.

User Startup

init

User Startup

Alarm

NO

NO

NO

YES

User has initiated either a Manual or Auto

Start-up from the Start-up/Shutdown

screen.

Input Contact

#1

Input Contact

#1

Alarm

YES

YES

NO

YES

The System has been notified from the OC-

DI option that a customer alarm has been

activated. The system will substitute user-

defined text when displaying these alarms.

Input Contact

#2

Input Contact

#2

Alarm

YES

YES

NO

YES

The System has been notified from the OC-

DI option that a customer alarm has been

activated. The system will substitute user-

defined text when displaying these alarms.

Input Contact

#3

Input Contact

#3

Alarm

YES

YES

NO

YES

The System has been notified from the OC-

DI option that a customer alarm has been

activated. The system will substitute user-

defined text when displaying these alarms.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)