Liebert 30-130kVA User Manual

Page 85

Advertising
background image

Operation

77

Inv I limit xfer

Inverter

Current Limit

Transfer

Fault

NO

YES

NO

YES

The instantaneous inverter current of any

one phase has exceeded its Pulse by Pulse

current limit value. An “Inverter Current

Limit” alarm was already issued and pulse

parallel operation was initiated. At the end

of pulse parallel the load current has not be

reduced below 150% The load will transfer

to Static Bypass. If the fault or over load

clears the unit will retransfer to UPS. Check

the total load compared to the UPS rating,

reduce load where necessary. If the UPS

does not retransfer when the load is below

100% of the rated load or if the unit shuts

down, contact Liebert Global Services

Immediately.

Batt ovtemp

cb trip

Battery

Overtemp CB

Trip

Fault

YES

YES

NO

YES

With the battery breaker closed and the

Battery Overtemp…Breaker Trip” option

enabled, the internal battery temperature

has exceeded its Maximum set point value.

The battery UV trip will be activate and the

battery will be disconnected from the UPS.

Battery Back up is no longer available.

Check the battery to determine the possible

cause of the overload and remove if

possible. Once the battery has cooled

below the set point temperature, the battery

may be brought on line again. If the

problem recurs contact Liebert Global

Services.

Batt gnd CB

trip

Batt gnd fault

CB trip

Fault

NO

YES

NO

YES

With BGF option installed, BGF breaker trip

enabled, and batt breaker closed, Comms

DPS sees its BGF input asserted by the

SWGR. It will issue a batt breaker UV trip

and motor op disable. To correct, repair and

restart batt via the MM. Contact Liebert

Global Services for assistance.

Byp pwr

supply fail

Bypass Power

Supply Fail

Fault

NO

YES

NO

YES

With Bypass source available, the UPS has

determined that the bypass power supply

has failed. The SBS will be turned off and

the contactors opened. SBS will not be

available. This fault will inhibit transfers and

start-up. Contact Liebert Global Services

immediately.

EPO

shutdown

EPO

Shutdown

Fault

NO

YES

NO

YES

The Emergency Power Off switch has been

pressed, which caused the UPS system to

shut down and remove all power from the

critical load. Determine the cause of the

emergency condition and correct it if

possible. Contact Liebert Global Services if

you require assistance.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)