Operation

85

System Fan

Fail

System Fan

Fail

Alarm

NO

YES

NO

YES

A fault in the designated Fan motor has

occurred. This condition only causes an

alarm, but if not promptly corrected it could

cause an equipment over-temperature

condition that would shut down the UPS

Module. Check the Fans for proper

operation. Contact Liebert Global Services

to replace a fan.

EPO Latched

EPO Latched

Alarm

NO

NO

NO

YES

During start up the EPO switch is sensed as

being activated. Startup is inhibited until the

alarm is cleared. Clear the latched EPO via

the push-button switch located on the

SWGR Board, then perform start up.

SBS

Unable

SBS Unable

Alarm

NO

NO

NO

YES

The UPS output is not synchronized to the

bypass power source, the static bypass

switch is disconnected, or it has failed

internally. Emergency and overload transfer

to the bypass source is not available. If the

module does not have a manual disconnect

switch, open and re-close the static switch

fuseholder. If the alarm conditions are

automatically corrected, reset the alarm to

clear it. Contact Liebert Global Services if

the alarm stays on.

Transfer To

Byp OK

Transfer To

Bypass OK

Alarm

YES

YES

NO

YES

Shows after a successful transfer to

Bypass. Display is only momentary.

Low batt

capacity

Reduced

Battery

Capacity

Alarm

YES

YES

NO

YES

Occurs on systems with multiple battery

cabinets. Indicates that at least one battery

breaker is on and one or more battery

breakers in the string are off. In this state,

the calculations for battery time remaining

and End of Discharge are adjusted

accordingly.

Inv Off by

User

Inv Off by User Alarm

YES

YES

NO

YES

The User has turned the inverter off through

the front panel. Puts data into the event

history log.

Batt Low

Warning

Battery Low

Warning

Alarm

YES

YES

NO

YES

With the battery breaker closed, the UPS

has determined that the DC bus voltage

has reached the user settable “Battery Low

Warning” set point. Complete the controlled

shutdown of the critical load. Reset the

alarms if the input power is restored before

shutdown.

Batt Test

Failed

Battery Test

Failed

Alarm

YES

YES

NO

YES

With the battery breaker closed, the battery

has failed the self-test. Momentary display.

Sets flag in the event history log

Batt Test

Passed

Battery Test

Passed

Alarm

NO

NO

NO

YES

With the battery breaker closed, the battery

has passed the self-test. Momentary

display. Sets flag in the event history log

Config

Modified

Config

Modified

Alarm

NO

NO

NO

YES

The User has modified and saved one or

more settings on the configuration screen.

Momentary display. Sets flag in the event

history log

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)