Liebert 30-130kVA User Manual

Page 87

Advertising
background image

Operation

79

Rectifier Fail

Rectifier Fail

Fault

YES

YES

YES

YES

This is a summary event based on the

detection of at least one of these faults

being active: Battery Overcharge; DC

Overvoltage Steady State; DC Overvoltage

Transient; DC Undervoltage Steady State;

Delta-Wye Current Imbalance; Rectifier

Fuse Fail; Rectifier Drive 1 Fail; Rectifier

Drive 2 Fail. All actions are controlled by the

causal fault.

Inverter Fail

Inverter Fail

Fault

YES

YES

YES

YES

This is a summary event based on the

detection of at least one of the following;

IDC Peak; IGBT Drive Fail; Output

Overvoltage Transfer; Output Undervoltage

Transfer; Inverter DC Offset. All actions are

controlled by the causal faults.

Ovtemp time-

out Sd

Overtemp

Time-out

Shutdown

Fault

YES

YES

NO

YES

An Equipment Over-temperature condition

has persisted for more than 10 minutes.

The load is transferred to the bypass line

and the UPS module is shut down. Check

the air intake, air exhaust, and filters before

attempting to start-up the UPS.

Transfer

Failed Sd

Transfer Failed

Shutdown

Fault

YES

YES

YES

YES

A transfer to Static Bypass was

unsuccessfully attempted and power to the

load was lost. Attempt to restart the system.

Contact Liebert Global Services.

Ctrl Fault

SBS on

Controller fault

SBS on

Fault

YES

YES

NO

YES

Indicates that the unit has transferred to

SBS without the knowledge of the UPSC. It

occurs when the UPSC’s Watchdog Fail

line is automatically asserted during a

UPSC reset. This is a permanent (latched)

condition which requires service. Contact

Liebert Global Services at once.

Hardware Sd

Hardware

Shutdown

Fault

YES

NO

NO

YES

At least one of the following alarm

conditions is present: Inverter Fault,

Rectifier Fuse Blown, Reverse Power, Over

load Shutdown, logic power supply failure,

or inverter output symmetry failure. The

load automatically transfers to the bypass

line. The UPS module is shut down and

isolated. Contact Liebert Global Services at

once. Do not attempt to reset the UPS.

Opt pwr

supply Fail

Option Power

Supply Fail

Fault

YES

YES

NO

YES

The Option Power Supply has failed.

Remote Alarm Status panels may be

disabled. Contact Liebert Global Service.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)