Liebert 30-130kVA User Manual

Page 89

Advertising
background image

Operation

81

Input

OverVoltage

Input Over

Voltage

Alarm

NO

NO

NO

YES

For all of these input problems the system

will supply power from the battery until the

end of discharge. At that point single input

systems will lose power to the load. Dual

input systems will attempt to transfer to

bypass if qualified and available. Call

Liebert Global Services for Assistance.

Input current

limit

Input Current

Limit

Alarm

NO

YES

NO

YES

The RMS input current has reached the

Input Current Limit setting. Check the UPS

load.

Battery CB

Open

Battery CB

Open

Alarm

NO

YES

NO

YES

The module battery circuit breaker (MBD) is

open. This circuit breaker might have been

opened either manually or automatically in

a UPS shutdown procedure. If the UPS is

operating with this breaker open, the critical

load is not protected from loss of the utility

source power. Manual closure of the battery

breaker is inhibited. You must use the front

panel to set up the sequence for manual

battery re-closure. Follow the instructions in

manual start-up.

Batt Supp

Active

Batt sup-

plement is

active

Alarm

NO

YES

NO

YES

This condition is indicated when the Batt

Discharging and Input Undervoltage alarms

are simultaneously active. The alarm will

clear when the Inp. Undervoltage alarm

clears and/or if the rectifier turns off and/or

if the Batt Dischg alarm clears.

Bypass Sync

Error

Bypass Sync

Error

Alarm

NO

YES

NO

YES

The bypass is out of sync to a sufficient

degree that transfer to Static Bypass is

inhibited. An interrupted transfer will be

permitted only in the case of a critical fault.

If this alarm persists, contact Liebert Global

Services.

Byp out

Tolerance

Bypass

Voltage Out of

Tolerance

Alarm

NO

YES

NO

YES

One or more bypass voltages is below 80%

or above 115% of the nominal value. If the

load is on UPS, and the unit is a dual input

unit, transfers to bypass will be inhibited. If

the unit is a single input unit, the system will

shut down. The Alarm will be cleared 5

seconds after all voltage are again with 85-

110% of nominal. If the load has been shut

down, re-start will be required.

Bypass Line

Fail

Bypass Line

Fail

Alarm

NO

YES

NO

YES

The bypass source has dropped below 35V

per phase. On single input units, the UPS

will shut down. On dual input units, transfer

to the bypass will be inhibited. The alarm

will be cleared five seconds after all

voltages again exceed 45V. If the unit is

already on Bypass when this occurs, power

to the load will be lost.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)