Liebert 30-130kVA User Manual

Page 86

Advertising
background image

Operation

78

Hsink ovtemp

limit

Heatsink

Overtemp

Limit

Fault

YES

YES

YES

YES

The maximum heat sink temperature limit

has been exceeded. (Should be preceded

by a “Heatsink” Overtemp Warning alarm).

The load will be transferred to the Static

Bypass if available. If the load was already

on SBS when this alarm occurred, the

system will shut down. The fault will clear

when the temperature falls below the

Heatsink Overtemp Warning threshold. (If

this fault doesn’t clear soon enough it will

lead to an “Overtemp Time-out Shutdown”).

If the unit is still running it will make an

attempt to auto-retransfer when the fault

clears. If the faults do not clear; contact

Liebert Global Services.

Inp pwr

supply fail

Input Power

Supply Fail

Fault

NO

YES

NO

YES

The input source is present, but the input

power supply has failed. The unit has

redundant power supplies on both the input

and the output. Contact Liebert Global

Services immediately.

Out pwr

supply fail

Output Power

Supply Fail

Fault

NO

YES

NO

YES

The output source is present, but the output

power supply has failed. The unit has

redundant power supplies on both the input

and the output. Contact Liebert Global

Services immediately.

Ups Ambient

Limit

UPS Ambient

Ot Limit

Fault

YES

YES

YES

YES

The Outlet air temperature has exceeded

its maximum set point. The UPS will

transfer the load to bypass if available. If

already on bypass the system will

shutdown. The fault will clear when the

temperature falls below the Outlet Air

Overtemp Warning threshold. (If this fault

doesn’t clear soon enough it will lead to an

“overtemp Time-out Shutdown”.). If the unit

is still running when the fault clears it will

auto retransfer to UPS. Check all air inlets

and exhausts for blockage and check the

air filter. Check the actual load against the

UPS rating. Remove any excess load.

Contact Liebert Global Services if the alarm

persists.

Pwr Supply

F1 Fail

Power Supply

F1 Fail

Fault

NO

YES

NO

YES

Failure of this fuse will remove control

power. The UPS will attempt to transfer to

Static Bypass if available. Locate the cause

of any failure, before replacing a fuse or

Contact Liebert Global Services

Immediately.

SWGR Power

Fail

SWGR Power

Fail

Fault

NO

YES

NO

YES

UPS will transfer to Static Bypass if

available and shut down the UPS. Start-up

will be inhibited. Contact Liebert Global

Services.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)