Operation

83

Inv Ovld

Phase C

Inverter

Overload

Phase C

Alarm

NO

YES

NO

YES

With the load on UPS, PhaseB output KVA

or KW or RMS current has exceeded 105%

of the nominal per phase rating. The UPS

will begin sending the time remaining until a

transfer or shutdown will occur, per the

Overload vs. Time Curve. The alarm

condition will clear when the overload

returns to below the nominal rating.

Low Pwr

Factor Warn

Low Power

Factor

Warning

Alarm

NO

YES

NO

YES

On any output phase that is supplying at

least 15% of its rated KVA, the measured

output power factor is below 0.50, leading

or lagging.

Pulse

Paralleling

Pulse Parallel

Activated

Alarm

NO

YES

NO

YES

With the load being supplied by the inverter,

the measured load current exceeds the

auto-Parallel Current Limit or the Pulse-by-

Pulse Current Limit set point values. If the

Static Bypass is available, the SBS supplies

supplemental power. If at the end of 10

cycles the load current has not returned to

below 105%, the Static Bypass will be left

on and the inverter will be turned off. If the

over current has cleared the Inverter will be

left on and the SBS will be turned off.

Auto rexfer

failed

Auto

Retransfer

Failed

Alarm

YES

YES

NO

YES

After performing a recoverable transfer to

bypass, with Auto Rexfer enabled, the Auto

Rexfer time out (default=5minutes) has

elapsed before retransfer could be

performed. A manual retransfer must be

performed, which will then clear the lockout

and zero the retransfer/ hour counter. If the

manual transfer is inhibited, the Inverter

may be latched off due to another fault.

Contact Liebert Global Services.

Excessive

Auto Rexfer

Excessive

Auto

Retransfer

Alarm

YES

YES

NO

YES

The UPS has determined that the actual

number of Auto Retransfers in the past hour

has exceeded the permitted maximum.

(user settable, default=5). This alarm

should not be issued if auto retransfers are

disabled by setting the maximum attempts

to “0”. A manual retransfer must be

performed, which will then clear the lockout

and zero the retransfer/hour counter.

Aux Power

Fail

Aux Power Fail Alarm

NO

YES

NO

YES

If the unit is supplying power to an Auxiliary

device, this alarm indicates that the system

has detected a failure in the Aux. Power

circuit.

EPO Power

Fail

EPO Power

Fail

Alarm

NO

YES

NO

YES

If the unit is supplying power to an Auxiliary

device, this alarm indicates that the system

has detected a failure in the Aux. Power

circuit.

LBS Power

Fail

LBS Power

Fail

Alarm

NO

YES

NO

YES

Power to the Load Bus Sync circuit has

been lost. Check external wiring. Contact

Liebert Global Services.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)