Liebert 30-130kVA User Manual

Page 84

Advertising
background image

Operation

76

Inverter Ovld

xfer

Inverter

Overload

Transfer

Fault

YES

YES

YES

YES

With the load on UPS, at least one phase of

the UPS KVA or KW has exceeded the

rated KVA, KW, or RMS current vs. Time

equation. (Note: This fault would have been

preceded by an “Inverter Overload Phase x

alarm.) The UPS will transfer the load to

Static Bypass if it is available. If the fault or

overload clears the UPS will automatically

transfer from SBS to UPS. Remove the

excess load from the UPS and attempt to

re-start. If the load is below the rating of the

UPS and it will not re-start, contact Liebert

Global Services.

Inverter Fuse

Fail

Inverter Fuse

Fail

Fault

YES

YES

NO

YES

One or more Output Fuses are open.

(because of capacitance in the system it

may take up to 1 minute after a fuse failure

to detect this fault). The system will transfer

the load to Static Bypass if available and

then shut down the UPS. Contact Liebert

Global Services Immediately.

Output Ov

xfer

Output

Overvolt

Transfer

Fault

NO

YES

YES

YES

The UPS module output voltage is above

the maximum (+10%) deviation from

nominal. The load automatically transfers to

the bypass line. The UPS module is shut

down and isolated. Contact Liebert Global

Services at once. Do not attempt to reset

circuit breakers.

Output Uv

xfer

Output

Undervolt

Transfer

Fault

NO

YES

YES

YES

The UPS module output voltage is under

the minimum (-12%) deviation from

nominal. The load automatically transfers to

the bypass line. If the alarm condition is no

longer present, reset the alarm and

retransfer the load from bypass to UPS.

Contact Liebert Global Services if alarm

persists.

SBS SCR

Open

SBS SCR

Open

Fault

YES

YES

NO

YES

This fault can only be detected when the

load is on bypass. One or more of the Static

Bypass phases are open. The static switch

will be shut down and the UPS will shut

down. Power to the load will be lost.

Contact Liebert Global Services

Immediately.

SBS SCR

Shorted

SBS SCR

Shorted

Fault

YES

YES

NO

YES

The system has detected a shorted SCR in

the Bypass line. If the unit is in the start-up

mode, start- up will be inhibited. If the unit is

on UPS, the unit will transfer to Bypass and

open the output contactor to prevent back

feed to the inverter from the Bypass line.

Contact Liebert Global Services

Immediately.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)