Operation

82

SBS Ovld

Phase A

SBS Overload

Phase A

Alarm

NO

NO

NO

YES

With the load on Static Bypass, the phase A

output kVA or kW or RMS current has

exceeded 115% of the nominal per-phase

kVA or kW or RMS current rating. The UPS

will show time remaining until a shutdown

will occur, per the Overload vs. time curve.

The alarm will clear when the overload falls

to below 110% of the rating.

SBS Ovld

Phase B

SBS Overload

Phase B

Alarm

NO

NO

NO

YES

With the load on Static Bypass, the phase B

output kVA or kW or RMS current has

exceeded 115% of the nominal per-phase

kVA or kW or RMS current rating. The UPS

will show time remaining until a shutdown

will occur, per the Overload vs. time curve.

The alarm will clear when the overload falls

to below 110% of the rating.

SBS Ovld

Phase C

SBS Overload

Phase C

Alarm

NO

NO

NO

YES

With the load on Static Bypass, the phase C

output kVA or kW or RMS current has

exceeded 115% of the nominal per-phase

kVA or kW or RMS current rating. The UPS

will show time remaining until a shutdown

will occur, per the Overload vs. time curve.

The alarm will clear when the overload falls

to below 110% of the rating.

Inverter I

Limit

Inverter

Current Limit

Alarm

NO

NO

NO

YES

The instantaneous inverter current of any

one phase has exceeded its pulse-by-pulse

current limit value. The UPS will shutdown

when the Current Overload vs. time curve is

exceeded.

Output OF/UF Output OF/UF

Alarm

NO

YES

NO

YES

Output frequency differs from the nominal

(60Hz) by more than 0.5Hz. No transfer or

shutdown occurs. Contact Liebert Global

Services at once.

Inv Ovld

Phase A

Inverter

Overload

Phase A

Alarm

NO

YES

NO

YES

With the load on UPS, Phase x output KVA

or KW or RMS current has exceeded 105%

of the nominal per phase rating. The UPS

will begin sending the time remaining until a

transfer or shutdown will occur, per the

Overload vs. Time Curve. The alarm

condition will clear when the overload

returns to below the nominal rating.

Inv Ovld

Phase B

Inverter

Overload

Phase B

Alarm

NO

YES

NO

YES

With the load on UPS, Phase A output kVA

or kW or RMS current has exceeded 105%

of the nominal per phase rating. The UPS

will begin sending the time remaining until a

transfer or shutdown will occur, per the

Overload vs. Time Curve. The alarm

condition will clear when the overload

returns to below the nominal rating.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)