80

Batt

Discharging

Battery

Discharge

Alarm

NO

YES

NO

YES

The battery is discharging. This occurs

whenever the battery supplies power to the

load for more than five seconds because of

input power failure, a rectifier problem, or

an overload condition. If the input power or

a source of auxiliary power is restored to

the UPS module, the UPS automatically

returns to normal operation. Watch the

battery voltage carefully. Reduce the load

(begin controlled shutdown) to extend the

battery back-up time. Start the back-up

generator, if available. Reset the UPS

alarms after the input power is restored.

The message clears after 30 seconds.

Input I

Imbalance

Input Current

Imbalance

Alarm

NO

YES

NO

YES

With input current levels above 30% of

nominal and all three phase voltages within

5% of each other, there is a difference

between any single input phase current and

the average input phase current of more

than 25%. The UPS will open the Input filter

Contactor. The alarm will clear when the

difference in current falls below 20%, but

the Input filter contactor will need to be

reset, using the front panel. Refer to

manual start up instructions.

Input Line Fail Input Line Fail

Alarm

NO

NO

NO

YES

The rectifier input line voltage is outside of

specified limits or the input circuit breaker is

opened while the battery circuit breaker

remains closed. The battery supplies power

to the critical load through the UPS inverter.

Input OF/UF

Input OF/UF

Alarm

NO

YES

NO

YES

The input frequency is > ± 5% of the

nominal frequency. The UPS will begin

using the battery to supply power, if by the

end of discharge the problem is not

corrected, for single input units power to the

load will be lost, for dual input units the

system will attempt transfer to Bypass if

qualified and available.

Input Phase

Loss

Input Phase

Loss

Alarm

NO

YES

NO

YES

For all of these input problems the system

will supply power from the battery until the

end of discharge. At that point single input

systems will lose power to the load. Dual

input systems will attempt to transfer to

bypass if qualified and available. Call

Liebert Global Services for Assistance.

Input

UnderVoltage

Input Under

Voltage

Alarm

NO

NO

NO

YES

For all of these input problems the system

will supply power from the battery until the

end of discharge. At that point single input

systems will lose power to the load. Dual

input systems will attempt to transfer to

bypass if qualified and available. Call

Liebert Global Services for Assistance.