Operation

84

Batt Gnd

Fault

Battery ground

fault alarm

Alarm

NO

YES

NO

YES

With the Batt Gnd Fault option installed and

the batt breaker closed, the DSP sees its

BGF input asserted by the SWGR. No

action required.

Aux Ovtemp

Warning

Aux Overtemp

Warning

Alarm

YES

YES

NO

YES

With the Auxiliary temp sensor installed, it

is reading 85% or more of the specified

Maximum Aux temperature set point value.

Batt Ovtemp

Warning

Battery

Overtemp

Warning

Alarm

NO

YES

NO

YES

With the battery breaker closed the battery

has exceeded the “Battery Temperature

Alarm Threshold” set point value.

Heatsink

Ovtemp

Heatsink

Overtemp

Warning

Alarm

NO

YES

NO

YES

Sensors on the power semiconductor

heatsinks detect temperatures above the

steady state limits for these components.

The control logic sets off the alarm but does

not shut down the UPS module if the

condition lasts less than 10 minutes. Check

the air intake, air exhaust, and filters.

Reduce the load or transfer it to bypass.

Contact Liebert Global Services if the alarm

persists.

Inlet Air

Ovtemp

Inlet Air

Overtemp

Warning

Alarm

NO

YES

NO

YES

The intake air to the UPS module exceeds

the specified maximum temperature. This

condition only causes an alarm, but should

be corrected immediately to prevent

equipment overheating. Check to make

sure nothing is blocking the inlet air and that

the air filter is clean.

Ups Ambient

OvTemp

UPS Ambient

OvTemp

Alarm

NO

YES

NO

YES

The Outlet air temperature has exceeded

85% of its “Maximum outlet air temperature”

limit.

Pwr pole Fan

1 Fail

Power pole

Fan 1 Fail

Alarm

NO

YES

NO

YES

A fault in the designated Fan motor has

occurred. This condition only causes an

alarm, but if not promptly corrected it could

cause an equipment over-temperature

condition that would shut down the UPS

Module. Check the Fans for proper

operation. Contact Liebert Global Services

if you require assistance or to replace a fan.

Pwr pole Fan

2 Fail

Power pole

Fan 2 Fail

Alarm

NO

YES

NO

YES

A fault in the designated Fan motor has

occurred. This condition only causes an

alarm, but if not promptly corrected it could

cause an equipment over-temperature

condition that would shut down the UPS

Module. Check the Fans for proper

operation. Contact Liebert Global Services

to replace a fan.

Pwr pole Fan

3 Fail

Power pole

Fan 3 Fail

Alarm

NO

YES

NO

YES

A fault in the designated Fan motor has

occurred. This condition only causes an

alarm, but if not promptly corrected it could

cause an equipment over-temperature

condition that would shut down the UPS

Module. Check the Fans for proper

operation. Contact Liebert Global Services

to replace a fan.

Table 7

Alarms, functions, and corrective actions (continued)

Actual

Alarm/fault

Name

Displayed

On Front

Panel

Description

of Alarm/

Fault

Fault

Or

Alarm

Latch

Mask

Dial

Mask

Freeze

Mask

Event Log

Mask

Meaning and Corrective Action(s)