Appendix E: Modbus Protocol

APPENDIX E

Modbus Protocol

Function 02 - Read Input Status

Address Word

0000 - 0001

Returns ok/alarm for each input queried. This is the current

input state, not the alarm status. It is one bit per input.

Function 04 - Read Input Registers

Address Word

0000 - 0028 Returns a 32 bit integer to represent the current input
value.

8 inputs, AC detect, and Battery level.

Function 03 - Read Holding Registers

Function 06 - Preset Holding Register

Function 10 - Preset Multiple Registers

Address Byte

01 System Parameters

00 Unit’s phone number 16

none

10 Dialing method

1 1:Tone 2:Pulse

Tone

12 Voice reps

1 0 to 10

3

14 Callback acknowledge

1 1:Yes 0:No

Yes

16 Max calling rounds

1 0 to 100

100

18 Rings till answer

1 1 to 20

1

1C Carrier wait time

1 0 to 60 sec

35