Serial Port Profiles

Modbus Slave Advanced Settings Field Descriptions

Configure the following parameters:

End IP Address

Displays the ending IP address of the TCP/Ethernet Modbus Slaves, based on
the Start IP address and the UID range (not supported for IPv6 addresses).

Field Format: IPv4 address

Protocol

Specify the protocol that is used between the Modbus Master and Modbus
Slave(s).

Data Options: TCP or UDP

Default: TCP

UDP/TCP Port

The destination port of the remote Modbus TCP Slave that the IOLAN will
connect to.

Range: 0-65535

Default: 502

TCP/UDP Port

The network port number that the Slave Gateway will listen on for both TCP
and UDP messages.

Default: 502

Next Request Delay A delay, in milliseconds, to allow serial slave(s) to re-enable receivers before

issuing next Modbus Master request.

Range: 0-1000

Default: 50 ms

Enable Serial
Modbus Broadcasts

When enabled, a UID of 0 (zero) indicates that the message will be broadcast to
all Modbus Slaves.

Default: Disabled

Request Queuing

When enabled, allows multiple, simultaneous messages to be queued and
processed in order of reception.

Default: Enabled